Technical characteristic data
Safety related characteristic data
Pl acc. to EN 13849
Pl e
PFH / architecture
3,0 * 10
-9 /
architecture class 4
SIL acc. to EN 61508
SIL 3
Proof test interval
20 years = max. utilization period
General data
Max. number of extension modules
2
Interface for extension modules
T-bus connector, pluggable in top-hat rail
Safe digital I
14 incl. 8 OSSD
Safe digital I/O
-
Safe digital Out
2
Safe analog In
-
Safe relay outputs
1
Signal outputs
2
Pulse outputs
2
Type of connection
Clamp-type terminals
Electrical data
Supply voltage
24 VDC / 2A
Tolerance
-15%, +20%
Power consumption
2.4 W
Ratings digital I
24 VDC; 20 mA, Type1 acc. to EN61131-2
Ratings digital O
24VDC; 250 mA
Ratings relays
24 VDC/2A
230 VAC/2A
Pulse outputs
Max. 250 mA
Supply voltage fuse protection
Max. 2 A
Environmental data
Temperature
0° to 50° operating temp.; -10° to +70 °
storage temp.
Class of protection
IP 52
Climatic category
3 acc. to DIN 50 178
EMC
In accordance with EN 55011 and EN 61000-6-2
Mechanical data
Dimensions (HxDxW [mm])
100x115x45
Weight
300 g
Fastening
To snap on standard rail
Max. conductor size
1.5 mm²