Installation manual
Page 135 of204
A 3147 / A 3148
Alarm message
Pulse2 plausibility fault on input DI9
Cause
Configured Pulse2 voltage not applied to this input.
Remedy
Check the configuration of the digital input DI9 acc. to planning
and circuit diagram
Check wiring
A 3149 / A 3150
Alarm message
Pulse2 plausibility fault on input DI10
Cause
Configured Pulse2 voltage not applied to this input.
Remedy
Check the configuration of the digital input DI10 acc. to planning
and circuit diagram
Check wiring
A 3151 / A 3152
Alarm message
Pulse2 plausibility fault on input DI11
Cause
Configured Pulse2 voltage not applied to this input.
Remedy
Check the configuration of the digital input DI11 acc. to planning
and circuit diagram
Check wiring
A 3153 / A 3154
Alarm message
Pulse2 plausibility fault on input DI12
Cause
Configured Pulse2 voltage not applied to this input.
Remedy
Check the configuration of the digital input acc. to planning and
circuit diagram
Check wiring
A 3155 / A 3156
Alarm message
Pulse2 plausibility fault on input DI13
Cause
Configured Pulse2 voltage not applied to this input.
Remedy
Check the configuration of the digital input acc. to planning and
circuit diagram
Check wiring
A 3157 / A 3158
Alarm message
Pulse2 plausibility fault on input DI14
Cause
Configured Pulse2 voltage not applied to this input.
Remedy
Check the configuration of the digital input acc. to planning and
circuit diagram
Check wiring
A 3159 / A 3160
Alarm message
Faulty 24V signal on DI1
Cause
No permanent 24V voltage applied to this input
Remedy
Check the voltage on the digital input!
Check wiring
Check whether Pulse1 or Pulse2 is applied