Installation manual
Page 19 of204
Technical characteristic data:
Safety related characteristic data
Pl acc. to EN 13849
Pl e
PFH / architecture
Type 2.6 * 10
-9 1)
/ Class 4
SIL acc. to EN 61508
SIL 3
Proof test interval
20 years = max. utilization period
General data
Safe digital I
12 incl. 8 OSSD
Safe digital I/O
10
Safe digital Out
-
Safe analog In
-
Safe relay outputs
-
Signal outputs
2
Pulse outputs
2
Type of connection
Clamp-type terminals
Electrical data
Power consumption
Max. 3.8 W
Ratings digital I
24 VDC; 20 mA, Type1 acc. to EN61131-2
Ratings digital O
24VDC; 250 mA
Pulse outputs
Max. 250 mA
Environmental data
Temperature
0° to 50° operating temp.; -10° to +70 °
storage temp.
Class of protection
IP 52
Climatic category
3 acc. to DIN 50 178
EMC
In accordance with EN 55011 and EN 61000-6-2
Mechanical data
Dimensions (HxDxW [mm])
100x115x45
Weight
300 g
Fastening
To snap on standard rail
Max. conductor size
1.5 mm²
1)
Value applies only for extension module. For a total assessment in accordance with EN 13849 one
must use a sries connection with the corresponding basic device => PFH
Logic
= PFH
Basic
+ PFH
Extension