4.3.3.1 Wiring examples basic outputs
4.3.3.1.1 Single-pole switching relay or semi-conductor output without test
For the connection of multi-phase applications or for higher current demands external contactors
may be used. For a single-pole connection without external test please bear in mind that the
PSCBR1X module will not recognize bonding of one or several external contacts. The following
circuit example is only limited suitable for safety applications, Pl b acc. to EN 13849-1 can
maximally be achieved!
DO0_P
X21
X14
DO0_M
DO1_P
DO1_M
DI1
DI2
DI3
DI4
L+
L-
Fig.: Single-pole switching P-output.
K1
K2
L+
L-
X22
Fig.: Single-pole switching relay output.
Safety note:
Not recommended for safety applications! In this context see also the notes in EN 13849-1
concerning the application and the required fault exclusions.