4.3.4 Configurable I/O as outputs
The extension module PSCBR-E-31-12DI-10DIO has 10 configurable safe I/O EAA1...EAA10
(see chapter 3 Module overview). Parameterized as an output this connection acts as a safe
digital Hi-Side output (DO_P).
4.3.4.1 Classification of the I/O when used as output
Architecture
Performance Level
Comment
Static single-channel
PL c
-
Fault detection or fault reaction acc. to
cat. 2
Static two-channel
PL e
-
Different group
Static two-channel
PL d
Same group:
-
Time-shifted triggering on PLC level
-
Fault approach short-circuit on both
outputs
Different group:
-
Nom further requirements necessary
Dynamically single-
channel
PL e
Nom further requirements necessary
Dynamically dual-
channel
PL e
Nom further requirements necessary
Note:
1)
G oup 1: EAA1 … EAA6
G oup 2: EAA7 … EAA10
2) Static: no pulse test on output
Dynamic: Pulse test on output with t
Test
≤ 500 µs
4.3.4.2 Wiring example for outputs of extension module
4.3.4.2.1 Wiring single-channel without testing
EAA1
X12
X21
EAA2
P1
P2
L+
L-
EAA3
EAA4
EAA5
EAA6
EAA7
EAA8
EAA9
EAA10
X22