Installation manual
Page 85 of204
Safety note:
The PSCBR module must be individually protected by a 2A/24VDC back-up fuse. single-
pole thermal magnetic circuit breaker with rapid acting characteristic
The power supply has to measure up with PELV standard in accordance to EN50178
Comments:
Reliable galvanic isolation from the 230 VAC or 400 VAC network must be guaranteed in any
case. This requires the selection of power supply units complying with the regulations
DIN VDE 0551, EN 60 742 and DIN VDE 0160. Besides choosing a suitable device you must
also ensure equipotent bonding between PE and 0-VDC on the secondary side.
IMPORTANT:
Signal GND of all external devices connected to the input interfaces of the PSCBR is to be
ensured as equipotent to PSCBR Supply GND.
Input interfaces are:
Digital inputs
Encoder inputs
Analog inputs
Remark:
Input lines GND_ENC and AIN
– are not connected internally to supply GND