Installation manual
Page 26 of27
8 Technical data
8.1
Environmental conditions
Class of protection
IP 20
Ambient temperature
0°C* ... 50°C
Climatic category
3 acc. to DIN 50 178
Lifetime
90000h at 50°C ambient
8.2 Load carrying capacity of outputs
The outputs can be loaded as follows:
Output
Voltage
Current
Ax.1, Ax.2
24 VDC
100 mA
EAAx.1-2
*)
24 VDC
250 mA
K1-K8
24 VDC
48 VDC
230 VAC/2A
2 A
2 A
2 A
Note:*) See the PSCBR-C-100 installation manual
8.3
Technical data of switching relay
Switching capacity min./max.
3 / 2000 (1 mVA / 7 VA)
Switching performance
According to IEC/EN 60947-5-
1 AC 15
According to IEC/EN 60947-5-
1 DC 13
At 0.1 Hz DC 13
250V / 3A
24 V / 1 A
24 V / 4 A
Electrical service life
50,000 switching cycles
Switching frequency
20 switching cycles / s
Mechanical service life
> 40 x 106 switching cycles