SFB-PN-IRT-8M12-IOP-V2

Operating instructions

Safety fieldbox

EN

Electrical data – Device ports X0 - X7: 

Maximum cable length:

 

30 m

Safety inputs: 

X1 and X2

Switching thresholds (acc. EN 61131, type 1):

 

−3 V … 5 V (Low) 

 

13 V … 30 V (High)

Current consumption per input:

 

< 6 mA / 24 V

Permissible residual drive current:

 

< 1.0 mA

Accepted test pulse duration on input signal:

 

 0.01 ms 

… 

1.0 ms

 

- With test pulse interval of:

 

20 ms … 120 s

Classification:

 

ZVEI CB24I  

Sink:

C1

Source:

C1

C2

C3

Test pulse outputs: 

Y1 and Y2

Switching elements:

 

p-type, short-circuit proof

Rated operating voltage U

e

 

24 VDC

Rated operating current I

e

:

 

Y1: 15 mA 

Y2: 10 mA at 24 V/30 mA at GND

Leakage current I

r

:

 

≤ 0.5 mA

Voltage drop U

d

:

 

≤ 1 V

Test pulse duration:

 

≤ 1 ms

Test pulse interval:

 

500 ms

Classification:

 

ZVEI CB24I  

Source:

C1

Sink:

C1

Digital output: 

DO

Switching elements:

 

2 p-type, short-circuit proof

Utilisation category:

 

DC-12 / DC-13

Rated operating voltage U

e

 

24 VDC

Rated operating current I

e

:

 

0.8 A

Leakage current I

r

:

 

≤ 0.5 mA

Voltage drop U

d

:

 

≤ 2 V

Inductive load:

 

≤ 400 mH

Switching frequency output:

 

≤ 1 Hz

Test pulse duration:

 

≤ 1 ms

Test pulse interval:

 

15 … 500 ms

Classification:

 

ZVEI CB24I  

Source:

C1

Sink:

C1

Diagnostics input/FB interface:  

DI

Switching thresholds:

 

−3 V … 5 V (Low) 

 

13 V … 30 V (High)

Current consumption per input:

 

< 12 mA / 24 V

Permissible residual drive current:

 

< 1.0 mA

Input debounce filter:

 

10 ms

FB interface data transmission rate:

 

19.2 kBaud

Power supply devices: 

A1 and A2

Rated operating voltage U

e

 

24 VDC

Rated operating current I

e

:

 

0.8 A

Device port line fuse:

 

1.5 A  

(integrated automatic resettable fuse)

Electrical data – PROFINET P1/P2 

Field bus protocol:

 

PROFINET / PROFIsafe

Specification:  

 

- PROFINET:

 

V2.3, Conformance class C  

  - Supported options:

 

MRP, fast start-up 

 

- PROFIsafe

 

V2.4

Network load class, PROFINET:

 

3

Transmission rate:

 

100 Mbit/s Full Duplex

PROFINET addressing:

 

via DCP

Integrated switch:

 

Dual port, 100 Mbit/s, IRT-capable

Supported PROFINET services:

 

I&M0 to I&M3, SNMP, LLDP

Service interface:

 

Web interface HTTP

LED indications 

8 x LED green/red 'E':

 

Error LED, device port  

8 x LED yellow 'I':

 

Input LED, device port

2 x LED green 'L':

 

Link LED, Ethernet port 

2 x LED green 'A':

 

Activity LED, Ethernet port

1 x LED green/red 'SF':

 

System fault LED  

1 x LED red 'BF':

 

Bus fault LED

1 x LED green/red 'Err':

 

Error LED, fieldbox 

1 x LED green 'Pwr':

 

Power LED, fieldbox

All fieldboxes have a good resistance against chemicals 

and oil. When used in aggressive media (e.g. chemicals, 

oils, lubricants and coolants in high concentrations) the 

material resistance must in each case be checked in 

advance for the specific application.

The sum of the total current of the individual device ports 

X0 – X7 for outputs A1 (power supply to devices) and DO 

(digital output) should not exceed 850 mA.

Protection class IP67 is only reached if all M12 connectors 

and blanking plugs, as well as the viewing window are 

properly fastening with screws.

2.4  Safety classification

- Safety inputs, 2-channel:

Standards:

 

EN ISO 13849-1, IEC 61508, EN 62061

PL:

 e

Control Category:

 4

DC:

 

99 %

PFH:

 

1.1 x 10

-9

 /h

PFD

avg

:

 

9.6 x 10

-5

SIL:

 

suitable for SIL 3 applications

Mission time:

 

20 years

Response time of local safety input > PROFINET:

 

20 ms

The SFB fulfills the requirements as PDDB according to EN 60947-5-3 

in combination with magnetic sensors (2 NC contacts) up to PL e / SIL 3.

- Safety inputs, 1-channel:

Standards:

 

EN ISO 13849-1, IEC 61508, EN 62061

PL:

 

d

Control Category:

 

2

DC:

 

90 %

PFH:

 

2.3 x 10

-7

 /h

PFD

avg

:

 

2.0 x 10

-2

SIL:

 

suitable for SIL 1 applications

Mission time:

 

20 years

Response time of local safety input > PROFINET:

 

20 ms

Test interval for error detection:

 

10 s

- Safety outputs, 1 wire (PL d):

Standards:

 

EN ISO 13849-1, IEC 61508, EN 62061

PL:

 d

Control Category:

 3 

DC:

 

90 %

PFH:

 

1.0 x 10

-7

 /h

PFD

avg

:

 

8.8 x 10

-3

SIL:

 

suitable for SIL 2 applications

Mission time:

 

20 years

PROFINET reaction time > local safety output:

 

50 ms

- Safety outputs, 2 wires (PL e):

Standards:

 

EN ISO 13849-1, IEC 61508, EN 62061

PL:

 e

Control Category:

 4

DC:

 

99 %

PFH:

 

1.2 x 10

-9

 /h

PFD

avg

:

 

1.1 x 10

-4

SIL:

 

suitable for SIL 3 applications

Mission time:

 

20 years

PROFINET reaction time > local safety output:

 

50 ms

This product must only be replaced in the application by an 

identical product of type SFB-PN-IRT-8M12-IOP-V2 with 

part no. 103040357.

The older product version has a lower safety level.

Summary of Contents for SFB-PN-IRT-8M12-IOP-V2

Page 1: ...se operating instructions are developed to execute safety related functions as part of an entire plant or machine It is the responsibility of the manufacturer of a machine or plant to ensure the corre...

Page 2: ...rds and the required safety level The non safe IO signals of the connected devices are connected to the control system via the field bus Safety switchgear with parallel IO signals can be connected to...

Page 3: ...LED device port 8 x LED yellow I Input LED device port 2 x LED green L Link LED Ethernet port 2 x LED green A Activity LED Ethernet port 1 x LED green red SF System fault LED 1 x LED red BF Bus fault...

Page 4: ...m Connecting cable male female connectors 103013428 5 0 m Connecting cable male female connectors 101217790 7 5 m Connecting cable male female connectors 103013429 10 0 m Connecting cable male female...

Page 5: ...xchangeable medium has been activated in the F CPU for the PROFINET interface under General Advanced options Interface options 4 3 Power supply and fuse protection The supply voltage of the safety fie...

Page 6: ...evice port X2 Input LED X2 Error LED X6 Device port X6 Input LED X6 Device port X0 X3 Device port X4 X7 with FB interface for BDF200 FB Error LED X1 Device port X1 Input LED X1 Error LED X0 Device por...

Page 7: ...ion Electrostatically sensitive components Do not touch the printed circuit board directly When you open the inspection window ensure that no moisture or excessive humidity penetrates into the fieldbo...

Page 8: ...ED may exhibit the following display and flashing pattern LED display Description GREEN ON Field box in RUN GREEN Flashes Module fault can be acknowledged RED ON Internal field box fault RED 3 Hz F_WD...

Page 9: ...and unlock functions In the event of delayed activation of the lock and unlock function larger systems are possible Device configuration version Max number of devices Equals number of fieldboxes Lengt...

Page 10: ...Electromechanical interlock unlocking function via 1 wire SFB X0 X7 Safety Switch 1 5 A1 DI 2 4 Y1 X1 6 7 Y2 X2 8 3 DO A2 8 3 1 5 2 4 6 7 Diag SCHMERSAL devices AZM 161 FB AZM 170 FB AZM150 ST Electro...

Page 11: ...cibly interrupted SFB X0 X7 2 4 Y1 X1 1 2 Safety Switch Safety Switch 6 7 Y2 X2 1 2 Different safety switchgear Optoelectronic AOPD 8 pin SFB X0 X7 Receiver 1 5 A1 DI 2 4 Y1 X1 6 7 Y2 X2 8 3 DO A2 8 7...

Page 12: ...ervice GmbH Am Grauen Stein 51105 K ln ID n 0035 EC prototype test certificate 01 205 5878 00 22 Person authorised for the compilation of the technical documentation Oliver Wacker M ddinghofe 30 42279...