3
SFB-PN-IRT-8M12-IOP-V2
Operating instructions
Safety fieldbox
EN
Electrical data – Device ports X0 - X7:
Maximum cable length:
30 m
Safety inputs:
X1 and X2
Switching thresholds (acc. EN 61131, type 1):
−3 V … 5 V (Low)
13 V … 30 V (High)
Current consumption per input:
< 6 mA / 24 V
Permissible residual drive current:
< 1.0 mA
Accepted test pulse duration on input signal:
0.01 ms
…
1.0 ms
- With test pulse interval of:
20 ms … 120 s
Classification:
ZVEI CB24I
Sink:
C1
Source:
C1
C2
C3
Test pulse outputs:
Y1 and Y2
Switching elements:
p-type, short-circuit proof
Rated operating voltage U
e
:
24 VDC
Rated operating current I
e
:
Y1: 15 mA
Y2: 10 mA at 24 V/30 mA at GND
Leakage current I
r
:
≤ 0.5 mA
Voltage drop U
d
:
≤ 1 V
Test pulse duration:
≤ 1 ms
Test pulse interval:
500 ms
Classification:
ZVEI CB24I
Source:
C1
Sink:
C1
Digital output:
DO
Switching elements:
2 p-type, short-circuit proof
Utilisation category:
DC-12 / DC-13
Rated operating voltage U
e
:
24 VDC
Rated operating current I
e
:
0.8 A
Leakage current I
r
:
≤ 0.5 mA
Voltage drop U
d
:
≤ 2 V
Inductive load:
≤ 400 mH
Switching frequency output:
≤ 1 Hz
Test pulse duration:
≤ 1 ms
Test pulse interval:
15 … 500 ms
Classification:
ZVEI CB24I
Source:
C1
Sink:
C1
Diagnostics input/FB interface:
DI
Switching thresholds:
−3 V … 5 V (Low)
13 V … 30 V (High)
Current consumption per input:
< 12 mA / 24 V
Permissible residual drive current:
< 1.0 mA
Input debounce filter:
10 ms
FB interface data transmission rate:
19.2 kBaud
Power supply devices:
A1 and A2
Rated operating voltage U
e
:
24 VDC
Rated operating current I
e
:
0.8 A
Device port line fuse:
1.5 A
(integrated automatic resettable fuse)
Electrical data – PROFINET P1/P2
Field bus protocol:
PROFINET / PROFIsafe
Specification:
- PROFINET:
V2.3, Conformance class C
- Supported options:
MRP, fast start-up
- PROFIsafe
V2.4
Network load class, PROFINET:
3
Transmission rate:
100 Mbit/s Full Duplex
PROFINET addressing:
via DCP
Integrated switch:
Dual port, 100 Mbit/s, IRT-capable
Supported PROFINET services:
I&M0 to I&M3, SNMP, LLDP
Service interface:
Web interface HTTP
LED indications
8 x LED green/red 'E':
Error LED, device port
8 x LED yellow 'I':
Input LED, device port
2 x LED green 'L':
Link LED, Ethernet port
2 x LED green 'A':
Activity LED, Ethernet port
1 x LED green/red 'SF':
System fault LED
1 x LED red 'BF':
Bus fault LED
1 x LED green/red 'Err':
Error LED, fieldbox
1 x LED green 'Pwr':
Power LED, fieldbox
All fieldboxes have a good resistance against chemicals
and oil. When used in aggressive media (e.g. chemicals,
oils, lubricants and coolants in high concentrations) the
material resistance must in each case be checked in
advance for the specific application.
The sum of the total current of the individual device ports
X0 – X7 for outputs A1 (power supply to devices) and DO
(digital output) should not exceed 850 mA.
Protection class IP67 is only reached if all M12 connectors
and blanking plugs, as well as the viewing window are
properly fastening with screws.
2.4 Safety classification
- Safety inputs, 2-channel:
Standards:
EN ISO 13849-1, IEC 61508, EN 62061
PL:
e
Control Category:
4
DC:
99 %
PFH:
1.1 x 10
-9
/h
PFD
avg
:
9.6 x 10
-5
SIL:
suitable for SIL 3 applications
Mission time:
20 years
Response time of local safety input > PROFINET:
20 ms
The SFB fulfills the requirements as PDDB according to EN 60947-5-3
in combination with magnetic sensors (2 NC contacts) up to PL e / SIL 3.
- Safety inputs, 1-channel:
Standards:
EN ISO 13849-1, IEC 61508, EN 62061
PL:
d
Control Category:
2
DC:
90 %
PFH:
2.3 x 10
-7
/h
PFD
avg
:
2.0 x 10
-2
SIL:
suitable for SIL 1 applications
Mission time:
20 years
Response time of local safety input > PROFINET:
20 ms
Test interval for error detection:
10 s
- Safety outputs, 1 wire (PL d):
Standards:
EN ISO 13849-1, IEC 61508, EN 62061
PL:
d
Control Category:
3
DC:
90 %
PFH:
1.0 x 10
-7
/h
PFD
avg
:
8.8 x 10
-3
SIL:
suitable for SIL 2 applications
Mission time:
20 years
PROFINET reaction time > local safety output:
50 ms
- Safety outputs, 2 wires (PL e):
Standards:
EN ISO 13849-1, IEC 61508, EN 62061
PL:
e
Control Category:
4
DC:
99 %
PFH:
1.2 x 10
-9
/h
PFD
avg
:
1.1 x 10
-4
SIL:
suitable for SIL 3 applications
Mission time:
20 years
PROFINET reaction time > local safety output:
50 ms
This product must only be replaced in the application by an
identical product of type SFB-PN-IRT-8M12-IOP-V2 with
part no. 103040357.
The older product version has a lower safety level.