Operating instructions

Safety fieldbox

SFB-PN-IRT-8M12-IOP-V2

EN

5.2  LED indicators, PROFINET ports P1/P2

There are 2 LED indicators at the Ethernet ports.

A green link LED and yellow activity LED.

LED link (L)

The link LED may exhibit the following display and flashing pattern:

LED display

Description

GREEN

ON

Connection to Ethernet active

LED Activity (A)

The activity LED may exhibit the following display and flashing pattern:

LED display

Description

YELLOW Flashes

Ethernet data transmission active

5.3  Central LED indicators, SFB-PN

There are 4 LEDs for central diagnostics of the fieldbox. A green/red 

LED indicator for a system fault, a red LED for bus fault, a green/red 

error LED and a green power LED.

System fault LED (SF)

The system fault LED may exhibit the following display and flashing 

pattern:

LED display

Description

RED

ON

Module error or device port error

GREEN

Flashes

FLASH signal for identifying the fieldbox

Bus fault LED (BF)

The bus fault LED may exhibit the following display and flashing 

pattern:

LED display

Description

RED

ON

No or slow connection

RED

Flashes

Connection but no data transmission

Fieldbox error LED (Err)

The error LED may exhibit the following display and flashing pattern:

LED display

Description

GREEN

ON

Field box in RUN

GREEN

Flashes

Module fault can be acknowledged

RED

ON

Internal field box fault

RED

3 Hz

F_WD_Time SFB-PN exceeded

RED

1 impulse

Internal over temperature fault

RED

2 impulses Invalid F address fault

RED

3 impulses

Invalid F_iPar_CRC fault

RED

4 impulses Acknowledge impulse length fault

RED

5 impulses Test pulse output overload fault

RED

6 impulses

Overvoltage fieldbox U > 29 V

Fieldbox power LED (Pwr)

The power LED may exhibit the following display and flashing pattern:

LED display

Description

GREEN

ON

Supply voltage of fieldbox OKAY

GREEN

1 Hz

Low voltage warning U < 20 V

GREEN

3 Hz

Low voltage fault U < 17 V

GREEN

OFF

Fieldbox switched off U < 12 V

6.  Set-up and maintenance

6.1  Functional testing

A check must be carried out to ensure that the projected safety function 

is effective.

The safety functions, configuration of the safety fieldbox and 

correct installation must be checked by a responsible safety 

specialist/safety representative.

6.2  Maintenance

The safety fieldbox operates error-free if installed and used properly.

7.  Disassembly and disposal

7.1  Disassembly

Only disassemble the safety fieldbox if it is in de-energized state.

7.2  Disposal

Dispose of the safety fieldbox properly in accordance with national 

regulations and laws.

Summary of Contents for SFB-PN-IRT-8M12-IOP-V2

Page 1: ...se operating instructions are developed to execute safety related functions as part of an entire plant or machine It is the responsibility of the manufacturer of a machine or plant to ensure the corre...

Page 2: ...rds and the required safety level The non safe IO signals of the connected devices are connected to the control system via the field bus Safety switchgear with parallel IO signals can be connected to...

Page 3: ...LED device port 8 x LED yellow I Input LED device port 2 x LED green L Link LED Ethernet port 2 x LED green A Activity LED Ethernet port 1 x LED green red SF System fault LED 1 x LED red BF Bus fault...

Page 4: ...m Connecting cable male female connectors 103013428 5 0 m Connecting cable male female connectors 101217790 7 5 m Connecting cable male female connectors 103013429 10 0 m Connecting cable male female...

Page 5: ...xchangeable medium has been activated in the F CPU for the PROFINET interface under General Advanced options Interface options 4 3 Power supply and fuse protection The supply voltage of the safety fie...

Page 6: ...evice port X2 Input LED X2 Error LED X6 Device port X6 Input LED X6 Device port X0 X3 Device port X4 X7 with FB interface for BDF200 FB Error LED X1 Device port X1 Input LED X1 Error LED X0 Device por...

Page 7: ...ion Electrostatically sensitive components Do not touch the printed circuit board directly When you open the inspection window ensure that no moisture or excessive humidity penetrates into the fieldbo...

Page 8: ...ED may exhibit the following display and flashing pattern LED display Description GREEN ON Field box in RUN GREEN Flashes Module fault can be acknowledged RED ON Internal field box fault RED 3 Hz F_WD...

Page 9: ...and unlock functions In the event of delayed activation of the lock and unlock function larger systems are possible Device configuration version Max number of devices Equals number of fieldboxes Lengt...

Page 10: ...Electromechanical interlock unlocking function via 1 wire SFB X0 X7 Safety Switch 1 5 A1 DI 2 4 Y1 X1 6 7 Y2 X2 8 3 DO A2 8 3 1 5 2 4 6 7 Diag SCHMERSAL devices AZM 161 FB AZM 170 FB AZM150 ST Electro...

Page 11: ...cibly interrupted SFB X0 X7 2 4 Y1 X1 1 2 Safety Switch Safety Switch 6 7 Y2 X2 1 2 Different safety switchgear Optoelectronic AOPD 8 pin SFB X0 X7 Receiver 1 5 A1 DI 2 4 Y1 X1 6 7 Y2 X2 8 3 DO A2 8 7...

Page 12: ...ervice GmbH Am Grauen Stein 51105 K ln ID n 0035 EC prototype test certificate 01 205 5878 00 22 Person authorised for the compilation of the technical documentation Oliver Wacker M ddinghofe 30 42279...

Reviews: