background image

9

SFB-PN-IRT-8M12-IOP

Operating instructions

Safety fieldbox

EN

8.  Configuration

8.1  Configuration examples of the power supply

If the power supply of each fieldbox is separated and in a star 

configuration, the maximum cable length of a fieldbox series is limited 

only by the maximum permissible cable length of the field bus used. 

If the power supply from fieldbox to fieldbox is looped through, 

the following maximum configurations apply.

3 different configurations are shown respectively for the different 

SCHMERSAL safety switchgear. One configuration with long cable 

lengths (maximum), one configuration with medium cable lengths 

(medium) and one configuration with shorter cable lengths (small).

The following assumptions are made for the configuration 

examples listed in the table:

•  The examples represent maximum configurations. If individual cable 

lengths are shortened, larger systems are possible.

•  2 x 1.5 mm² power supply wiring and 10 A fuse protection.

•  Use of SCHMERSAL cables.

•  The cable lengths listed in the table between the power supply and 

the first fieldbox as well as the individual fieldboxes are the maximum 

lengths. Reducing the individual cable lengths is not critical.

•  For interlocks, these designs are based on simultaneous activation of 

all lock and unlock functions. In the event of delayed activation of the 

lock and unlock function, larger systems are possible.

Device / configuration 

version

Max. number  

of devices

Equals number 

of fieldboxes

Length of the cable (A)  

up to the first fieldbox

Length of the cables (B)  

between the fieldboxes

Length of stub cables (C)  

for device connection

AZM 201 / Maximum

16

2

10.0 m

10.0 m

7.5 m

AZM 201 / Medium

20

2,5

7.5 m

7.5 m

5.0 m

AZM 201 / Small

24

3

7.5 m

5 m

3.5 m

MZM 100 / Maximum

20

2,5

10.0 m

10.0 m

7.5 m

MZM 100 / Medium

24

3

7.5 m

7.5 m

5.0 m

MZM 100 / Small

28

3,5

7.5 m

5 m

3.5 m

AZM 300 / Maximum

28

3,5

10.0 m

10.0 m

7.5 m

AZM 300 / Medium

32

4

7.5 m

7.5 m

5.0 m

AZM 300 / Small

40

5

7.5 m

5 m

3.5 m

AZM 400 / Maximum

16

2

10.0 m

10.0 m

7.5 m

AZM 400 / Medium

16

2

7.5 m

7.5 m

5.0 m

AZM 400 / Small

16

2

7.5 m

5 m

3.5 m

AZM 1xx / Maximum

20

2,5

10.0 m

10.0 m

7.5 m

AZM 1xx / Medium

24

3

7.5 m

7.5 m

5.0 m

AZM 1xx / Small

28

3,5

7.5 m

5 m

3.5 m

RSS & CSS / Maximum

48

6

10.0 m

10.0 m

7.5 m

RSS & CSS / Medium

56

7

7.5 m

7.5 m

5.0 m

RSS & CSS / Small

64

8

7.5 m

5 m

3.5 m

Mixed / Maximum

24

3

10.0 m

10.0 m

7.5 m

Mixed / Medium

28

3,5

7.5 m

7.5 m

5.0 m

Mixed / Small

32

4

7.5 m

5 m

3.5 m

Mixed fitting of fieldbox:

 2 x AZM 201, 2 x MZM 100, 2 x AZM 300 and 2 x RSS / CSS

Power

(A)

(B)

(B)

(C)

24 VDC

1

2

(C)

...

1

2

7

8

(C)

...

1

2

7

8

Fuse

10 A

Power supply

Fieldbox

Fieldbox

Fieldbox

Devices

Devices

Devices

Fuse

Summary of Contents for SFB-PN-IRT-8M12-IOP

Page 1: ...rsions or for applications that are approved by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instruction...

Page 2: ...mation on the commissioning of the safety SFB PN fieldbox can be found on the internet at www schmersal net GSDML file for safety fieldbox SFB PN The dual language GSDML file for the SFB PN can be fou...

Page 3: ...DO digital output should not exceed 850 mA Protection class IP67 is only reached if all M12 connectors and blanking plugs as well as the viewing window are properly fastening with screws 2 4 Safety c...

Page 4: ...nnector 103013430 10 0 m Pre wired cable female connector 103013431 3 0 m Connecting cable male female connectors 103013432 5 0 m Connecting cable male female connectors 103013433 7 5 m Connecting cab...

Page 5: ...3 Internal fuse elements device ports The device ports X0 X7 are designed for 0 8 A continuous current and equipped in each case with an auto resettable fuse of 1 5 A for line protection If the fuse e...

Page 6: ...ice port X2 Input LED X2 Error LED X6 Device port X6 Input LED X6 Device port X0 X3 Device port X4 X7 with FB interface for BDF200 FB Error LED X1 Device port X1 Input LED X1 Error LED X0 Device port...

Page 7: ...rostatically sensitive components Do not touch the printed circuit board directly When you open the inspection window ensure that no moisture or excessive humidity penetrates into the fieldbox The 3 r...

Page 8: ...may exhibit the following display and flashing pattern LED display Description GREEN ON Field box in RUN GREEN Flashes Module fault can be acknowledged RED ON Internal field box fault RED 3 Hz F_WD_T...

Page 9: ...igns are based on simultaneous activation of all lock and unlock functions In the event of delayed activation of the lock and unlock function larger systems are possible Device configuration version M...

Page 10: ...00 Electromechanical interlock interlock function via 1 wire SFB X0 X7 Safety Switch 1 5 A1 DI 2 4 Y1 X1 6 7 Y2 X2 8 3 DO A2 8 3 1 5 2 4 6 7 Diag SCHMERSAL devices AZM 161 FB AZM 170 FB Electronic sen...

Page 11: ...cibly interrupted SFB X0 X7 2 4 Y1 X1 1 2 Safety Switch Safety Switch 6 7 Y2 X2 1 2 Different safety switchgear Optoelectronic AOPD 8 pole SFB X0 X7 Receiver 1 5 A1 DI 2 4 Y1 X1 6 7 Y2 X2 8 3 DO A2 8...

Page 12: ...land Industrie Service GmbH Alboinstr 56 12103 Berlin ID n 0035 EC prototype test certificate 01 205 5719 00 19 Person authorised for the compilation of the technical documentation Oliver Wacker M ddi...

Reviews: