Operating instructions

Safety fieldbox

SFB-PN-IRT-8M12-IOP

EN

The information contained in this operating instructions manual is 

provided without liability and is subject to technical modifications. There 

are no residual risks, provided that the safety instructions as well as 

the instructions regarding mounting, commissioning, operation and 

maintenance are observed.

1.6  Warning about misuse

In the event of improper or unintended use or tampering,  

use of the safety fieldbox could expose persons to danger  

or cause damage to the machine or system components.

1.7  Exclusion of liability

We shall accept no liability for damages and malfunctions resulting from 

defective mounting or failure to comply with this operating instructions 

manual. The manufacturer shall accept no liability for damages 

resulting from the use of unauthorised spare parts or accessories.

For safety reasons, invasive work on the device as well as arbitrary 

repairs, conversions and modifications to the device are strictly 

forbidden; the manufacturer shall accept no liability for damages 

resulting from such invasive work, arbitrary repairs, conversions and/or 

modifications to the device.

2.  Product description

2.1  Ordering code

This operating instructions manual applies to the following types:

SFB-PN-IRT-8M12-IOP
Option

Description

SFB

Safety fieldbox

PN

PROFINET

IRT

Switch IRT-capable

8M12

8 device connectors for M12 connector, 8-pole 

IOP

Device connection: IO parallel

2.2  Purpose

The SFB-PN-IRT-8M12-IOP safety fieldbox is designed for connection 

 

of up to 8 safety switchgear units with parallel IO signals to a 

PROFINET/PROFIsafe network.

A maximum of 4 BDF200-FB control panels can be connected.

The safety signals from the connected safety switchgear are forwarded 

to a safety controller via the safety field bus for evaluation.

For larger safety applications, multiple fieldboxes can be connected to 

the power supply and field bus in series.

The user must evaluate and design the safety chain in 

accordance with the relevant standards and the required 

safety level.

The non-safe IO signals of the connected devices are connected to the 

control system via the field bus.

Safety switchgear with parallel IO signals can be connected to  

device ports X0 - X7.

BDF200-FB control panels can only be connected to  

device ports X4 - X7.

Manual: Safety fieldbox SFB-PN

Further information on the commissioning of the safety  

SFB-PN fieldbox can be found on the internet at 

 

www.schmersal.net.

GSDML file for safety fieldbox SFB-PN

The dual-language GSDML file for the SFB-PN can be found 

on the internet at www.schmersal.net after searching 'SFB'. 

A GSDML file is also saved in the device. The file can be 

downloaded via the integrated web server (see 'Info' page).

2.3  Technical data

Standards:

 

EN 61131-1, EN 61131-2, IEC 60947-5-3, 

 

ISO 13849-1, IEC 61508, IEC 62061

Time to readiness:

 

≤ 8 s

Worst Case Delay Time Input to DIN EN 61784-3-3:

 

≤ 20 ms

Worst Case Delay Time Output to DIN EN 61784-3-3:

 

≤ 50 ms

Device Watchdog Time to DIN EN 61784-3-3:

 

10 ms

Device Acknowledgement Time to DIN EN 61784-3-3:

 

≤ 25 ms

Materials: 

 

- Enclosure:

 

polyamide / PA 6 GF  

- Viewing window:

 

polyamide / PACM 12  

- Encapsulation:

 

polyurethane / 2K PU  

- Labelling plates:

 

polycarbonate / PC

Mechanical data 

Electrical connection version: 

 

Connector socket / connector 

Device ports X0 - X7:

 

M12/8-pole, A-coded 

- Power I/O:

 

M12-POWER/4-pole, T-coded

 

- PROFINET P1/P2:

 

M12/4-pole, D-coded

M12 connector tightening torque:

 

max. 1.5 Nm

 

- Recommended for Schmersal cables:

 

1.0 Nm

Fixing screws:

 

2 x M6  

- Tightening torque:

 

max. 3.0 Nm

Viewing window screws:

 

2 x Torx 10 

 

- Tightening torque:

 

0.5 … 0.6 Nm

Ambient conditions 

Ambient temperature:

 

−25 °C … +55 °C

Storage and transport temperature:

 

−25 °C … +70 °C

Relative humidity:

 

10 % … 95 %, non condensing

Resistance to shock:

 

30 g / 11 ms

Resistance to vibration:

 

5 … 10 Hz, amplitude 3.5 mm; 

 

10 … 150 Hz, amplitude 0.35 mm / 5 g

Protection type:

 

IP65/IP67 to IEC 60529

Protection class:

 III

Insulation values to IEC 60664-1: 

 

- Rated insulation voltage U

i

:

 

32 VDC  

- Rated impulse withstand voltage U

imp

:

 

0.8 kV 

 

- Over-voltage category:

 III 

 

- Degree of pollution:

 3

Electrical data - Power I/O 

Supply voltage U

B

:

 

24 VDC -15% / +10% 

 

(stabilised PELV mains unit)

Rated operating voltage U

e

 

24 VDC

Rated operating current I

e

:

 

10 A 

 

(external fuse protection required)

Current consumption SFB:

 

200 mA

Electrical data - Device ports X0 - X7 

Maximum cable length:

 

10 m

Safety inputs: 

X1 and X2

Switching thresholds 

(acc. EN 61131, type 1)

:

 

−3 V … 5 V (Low) 

 

13 V … 30 V (High)

Current consumption per input:

 

< 6 mA / 24 V

Permissible residual drive current:

 

< 1.0 mA

Accepted test pulse duration on input signal:

 

 0.01 ms 

… 

1.0 ms

 

- With test pulse interval of:

 

20 ms … 120 s

Classification:

 

ZVEI CB24I  

Sink:

C1

Source:

C1

C2

C3

All fieldboxes have a good resistance against chemicals 

and oil. When used in aggressive media (e.g. chemicals, 

oils, lubricants and coolants in high concentrations) the 

material resistance must in each case be checked in 

advance for the specific application.

Summary of Contents for SFB-PN-IRT-8M12-IOP

Page 1: ...rsions or for applications that are approved by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instruction...

Page 2: ...mation on the commissioning of the safety SFB PN fieldbox can be found on the internet at www schmersal net GSDML file for safety fieldbox SFB PN The dual language GSDML file for the SFB PN can be fou...

Page 3: ...DO digital output should not exceed 850 mA Protection class IP67 is only reached if all M12 connectors and blanking plugs as well as the viewing window are properly fastening with screws 2 4 Safety c...

Page 4: ...nnector 103013430 10 0 m Pre wired cable female connector 103013431 3 0 m Connecting cable male female connectors 103013432 5 0 m Connecting cable male female connectors 103013433 7 5 m Connecting cab...

Page 5: ...3 Internal fuse elements device ports The device ports X0 X7 are designed for 0 8 A continuous current and equipped in each case with an auto resettable fuse of 1 5 A for line protection If the fuse e...

Page 6: ...ice port X2 Input LED X2 Error LED X6 Device port X6 Input LED X6 Device port X0 X3 Device port X4 X7 with FB interface for BDF200 FB Error LED X1 Device port X1 Input LED X1 Error LED X0 Device port...

Page 7: ...rostatically sensitive components Do not touch the printed circuit board directly When you open the inspection window ensure that no moisture or excessive humidity penetrates into the fieldbox The 3 r...

Page 8: ...may exhibit the following display and flashing pattern LED display Description GREEN ON Field box in RUN GREEN Flashes Module fault can be acknowledged RED ON Internal field box fault RED 3 Hz F_WD_T...

Page 9: ...igns are based on simultaneous activation of all lock and unlock functions In the event of delayed activation of the lock and unlock function larger systems are possible Device configuration version M...

Page 10: ...00 Electromechanical interlock interlock function via 1 wire SFB X0 X7 Safety Switch 1 5 A1 DI 2 4 Y1 X1 6 7 Y2 X2 8 3 DO A2 8 3 1 5 2 4 6 7 Diag SCHMERSAL devices AZM 161 FB AZM 170 FB Electronic sen...

Page 11: ...cibly interrupted SFB X0 X7 2 4 Y1 X1 1 2 Safety Switch Safety Switch 6 7 Y2 X2 1 2 Different safety switchgear Optoelectronic AOPD 8 pole SFB X0 X7 Receiver 1 5 A1 DI 2 4 Y1 X1 6 7 Y2 X2 8 3 DO A2 8...

Page 12: ...land Industrie Service GmbH Alboinstr 56 12103 Berlin ID n 0035 EC prototype test certificate 01 205 5719 00 19 Person authorised for the compilation of the technical documentation Oliver Wacker M ddi...

Reviews: