SFB-PN-IRT-8M12-IOP

Operating instructions

Safety fieldbox

EN

4.  Electrical connection

4.1  General information for electrical connection

To supply the safety fieldbox, M12 power connectors, cables with a 

cross-section of max. 1.5 mm² can be connected to the fieldbox.

The electrical connection may only be carried out by  

authorised personnel in a de-energised condition.

4.2  Power supply and fuse protection

Secure the supply voltage of the safety fieldbox with a 10 A fuse. In 

order to increase the cable cross section for the supply voltage of the 

fieldbox, both connections from Us and GND must be connected in 

parallel. Pins 1 + 4 and 2 + 3 in the fieldbox are bridged.

0 VDC

+24 VDC

Power

10A

BN

1

BK

4

3
2

BU
WH

SFB

1
4

3
2

I   Power   O

GND

GND

Us

Us

4.3  Internal fuse elements device ports

The device ports X0 - X7 are designed for 0.8 A continuous current 

and equipped in each case with an auto-resettable fuse of 1.5 A for line 

protection. If the fuse element is triggered, the red LED on the device 

port flashes with 4 pulses.

After eliminating the overload at one of the device ports, the fuse resets 

itself after a short cool-down phase.

X0 – X7

1
2

A1

1,5A

8

...

4.4  Earth concept and shielding

A functional earth is connected for fault-free operation of the safety 

fieldbox. Earth loops must be avoided when connecting the functional 

earth.

The FE functional earth is normally connected via the switch. In the 

event of EMC problems, the fieldbox can be earthed via the separate 

FE connection.

An earth strap is available as an accessory.

Wiring examples for avoidance of earth loops:

FE

SFB

P1

P2

Ethernet

FE

SPS / 

Switch

FE

SFB

P1

P2

Ethernet

PLC /

FE

SFB

P1

P2

Ethernet

FE

SPS / 

Switch

FE

SFB

P1

P2

Ethernet

PLC /

Summary of Contents for SFB-PN-IRT-8M12-IOP

Page 1: ...rsions or for applications that are approved by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instruction...

Page 2: ...mation on the commissioning of the safety SFB PN fieldbox can be found on the internet at www schmersal net GSDML file for safety fieldbox SFB PN The dual language GSDML file for the SFB PN can be fou...

Page 3: ...DO digital output should not exceed 850 mA Protection class IP67 is only reached if all M12 connectors and blanking plugs as well as the viewing window are properly fastening with screws 2 4 Safety c...

Page 4: ...nnector 103013430 10 0 m Pre wired cable female connector 103013431 3 0 m Connecting cable male female connectors 103013432 5 0 m Connecting cable male female connectors 103013433 7 5 m Connecting cab...

Page 5: ...3 Internal fuse elements device ports The device ports X0 X7 are designed for 0 8 A continuous current and equipped in each case with an auto resettable fuse of 1 5 A for line protection If the fuse e...

Page 6: ...ice port X2 Input LED X2 Error LED X6 Device port X6 Input LED X6 Device port X0 X3 Device port X4 X7 with FB interface for BDF200 FB Error LED X1 Device port X1 Input LED X1 Error LED X0 Device port...

Page 7: ...rostatically sensitive components Do not touch the printed circuit board directly When you open the inspection window ensure that no moisture or excessive humidity penetrates into the fieldbox The 3 r...

Page 8: ...may exhibit the following display and flashing pattern LED display Description GREEN ON Field box in RUN GREEN Flashes Module fault can be acknowledged RED ON Internal field box fault RED 3 Hz F_WD_T...

Page 9: ...igns are based on simultaneous activation of all lock and unlock functions In the event of delayed activation of the lock and unlock function larger systems are possible Device configuration version M...

Page 10: ...00 Electromechanical interlock interlock function via 1 wire SFB X0 X7 Safety Switch 1 5 A1 DI 2 4 Y1 X1 6 7 Y2 X2 8 3 DO A2 8 3 1 5 2 4 6 7 Diag SCHMERSAL devices AZM 161 FB AZM 170 FB Electronic sen...

Page 11: ...cibly interrupted SFB X0 X7 2 4 Y1 X1 1 2 Safety Switch Safety Switch 6 7 Y2 X2 1 2 Different safety switchgear Optoelectronic AOPD 8 pole SFB X0 X7 Receiver 1 5 A1 DI 2 4 Y1 X1 6 7 Y2 X2 8 3 DO A2 8...

Page 12: ...land Industrie Service GmbH Alboinstr 56 12103 Berlin ID n 0035 EC prototype test certificate 01 205 5719 00 19 Person authorised for the compilation of the technical documentation Oliver Wacker M ddi...

Reviews: