2 Product description
19
Manual parameterization of the stability time filter:
For very difficult applications with extremely bouncing safeguards, the stable time
and the monitoring time can also be set manually.
For each device port there are 2 parameters for configuring the stable time filter.
Parameters
Value range
Default settings
Stable time
0.1 – 2.0 s
0.1 s for devices with OSSDs
0.7 s for devices with dry contacts
Monitoring time
1 – 20 s
2 s for devices with OSSDs
10 s for devices with dry contacts
INFORMATION
For manual parameterization, please ensure that the monitoring time
is at least 5 times longer than the set stable time.
Frequency limit of the input signal:
The maximum switching frequency of the input signal depends on the adjusted
stability time.
The switch-on time and also the switch-off time of the input signal must both be
present at the input for at least 2 x the adjusted stable time.
The cut-off frequency of the input signal is therefore 2.5 Hz if the lowest stability
time of 0.1 s has been adjusted.