2 Product description
2.4 Technical Data
2.4.1
General technical Data
Designation
Value
Standards
EN 61131-1, EN 61131-2, IEC 60947-5-3,
ISO 13849-1, IEC 61508, IEC 62061
Time to readiness
≤
8 s
Worst Case Delay Time (WCDT_Input / DIN EN 61784-3-3)
≤
20 ms
Worst Case Delay Time (WCDT_Output / DIN EN 61784-3-3)
≤
50 ms
Device Watchdog Time (Device_WD / DIN EN 61784-3-3)
10 ms
Device Acknowledgement Time (DAT / DIN EN 61784-3-3)
≤
25 ms
Materials
Enclosure
Polyamide / PA 6 GF
Viewing window
Polyamide / PACM 12
Encapsulation
Polyurethane / 2K PU
Labelling plates
Polycarbonate / PC
Mechanical Data
Electrical connection version
Device ports X0 – X7
Power I/O
PROFINET P1/P2
Build in socket / connector
M12 / 8-polig, A-coded
M12-POWER / 4-polig, T-coded
M12 / 4-polig, D-coded
M12 connector tightening torque
Recommended for SCHMERSAL cables
max. 1.5 Nm
1.0 Nm
Fixing screws
Tightening torque
2x M6
max. 3.0 Nm
Viewing window screws
Tightening torque
2x Torx 10
0.5 … 0.6 Nm
Ambient conditions
Ambient temperature
-25°C ... +55°C
Storage and transport temperature
-25°C ... +70°C
Relative humidity
10 % … 95 %, non-condensing
Resistance to shock
30 g / 11 ms
Resistance to vibration
5 … 10 Hz, amplitude 3.5 mm
10 … 150 Hz, amplitude 0.35 mm / 5 g
Protection type
IP65 / IP67 to IEC 60529
Protection class
III
Insulation values to IEC 60664-1
Rated insulation voltage U
i
Rated impulse withstand voltage U
imp
Over-voltage category
Degree of pollution
32 VDC
0.8 kV
III
3
CAUTION
Protection class IP67 is only reached if all M12 connectors and blanking plugs,
as well as the viewing window are properly fastening with screws.
CAUTION
All fieldboxes have a good resistance against chemicals and oil.
When used in aggressive media (e.g. chemicals, oils, lubricants and coolants in
high concentrations) the material resistance must in each case be checked in
advance for the specific application.