2 Product description
29
2.5.2
Safety inputs 1-channel
Designation
Value
Standards
IEC 61508, IEC 62061, ISO 13849-1
PL
d
Category
2
DC
90 %
PFH
2.3 x 10
-7
/h
PFD
avg
2.0 x 10
-2
SIL
suitable for SIL 1 applications
Mission time
20 years
Response time of local safety input > PROFINET
20 ms
Test interval for error detection
10 s
2.5.3
Safety outputs 1 wire (PLd)
Designation
Value
Standards
IEC 61508, IEC 62061, ISO 13849-1
PL
d
Category
3
PFH
1.0 x 10
-7
/h
PFD
avg
8.8 x 10
-3
SIL
suitable for SIL 2 applications
Mission time
20 years
PROFINET reaction time > local safety output
50 ms
2.5.4
Safety outputs 2 wires (PLe)
Designation
Value
Standards
IEC 61508, IEC 62061, ISO 13849-1
PL
e
Category:
4
PFH
2.9 x 10
-9
/h
PFD
avg
2.5 x 10
-4
SIL
suitable for SIL 3 applications
Mission time
20 years
PROFINET reaction time > local safety output
50 ms
WARNING
The safety functions, configuration of the safety fieldbox and correct installation
must be checked by a responsible safety specialist/safety representative.