4 Set-up
45
4.3 PROFINET configuration
4.3.1
Project engineering
When projecting PROFINET devices, a device is mapped as a modular system
with a header module and several data modules.
The safety fieldbox SFB-PN has the 3 data modules
−
FS data
−
Functional data
−
Diagnosis and FB-Interface
The address assignment and the data areas of the 3 modules are described
in Chapter 4.3.6.
The project engineering of the SFB-PN should be done in the following steps
−
Install GSDML file of SFB-PN
−
Add the SFB-PN module to the hardware configuration
−
Configuring SFB-PN in the PROFINET network
(IP address & PROFINET name)
−
Set the F address (PROFIsafe address) on the field box by using the
rotary coding switches and configure it in the configuration software
−
Configure safety parameters in the F-PLC
−
Set F_WD_Time depending on the polling cycle of the safety program
in the F-PLC.
−
Execute safety validation with the SFB Configuration Tool
−
Transfer F_iPar_CRC to the F-PLC
−
Implementing a program for the acknowledgement of module faults
and device port faults
−
Download configuration from the engineering software to the F-PLC