48
4 Set-up
4.3.4
Setting the F-address and factory reset
The 3 rotary coding switches behind the viewing window can be used to set the
safety address and to carry out a factory reset of the SFB.
Carefully remove the viewing window. (Screws Torx 10)
CAUTION
The screws in the viewing window are not locked!
Keep the screws safe so that they do not get lost.
CAUTION
When you open the inspection window, ensure that no moisture or excessive
humidity penetrates into the fieldbox.
CAUTION
Electrostatically sensitive components!
Do not touch the printed circuit board directly.
x 100
x 10
x 1
F address
0 0 1 … 9 9 9 Valid F address
0 0 0
Factory reset
Setting of the F address
•
Remove power from the SFB
•
Set F address in the range 1 - 999
•
Supply with voltage again
Carrying out an SFB factory reset
•
Remove power from the SFB
•
Setting of F address 0 – 0 – 0
•
Supply with voltage again
•
After 1 minute, switch off the power of the SFB-PN again
The IP address and the PROFINET name are deleted during a factory reset.