5 Diagnostic system
67
Error No. Error message
Help information / Note
Fault Pulse-Outputs
Cross-fault Pulse-Outputs at Device-Port
1030
Fault: pulse outputs Device-Port X0
Cross-fault pulse outputs X0,
check cord set and device.
1031
Fault: pulse outputs Device-Port X1
Cross-fault pulse outputs X1,
check cord set and device.
1032
Fault: pulse outputs Device-Port X2
Cross-fault pulse outputs X2,
check cord set and device.
1033
Fault: pulse outputs Device-Port X3
Cross-fault pulse outputs X3,
check cord set and device.
1034
Fault: pulse outputs Device-Port X4
Cross-fault pulse outputs X4,
check cord set and device.
1035
Fault: pulse outputs Device-Port X5
Cross-fault pulse outputs X5,
check cord set and device.
1036
Fault: pulse outputs Device-Port X6
Cross-fault pulse outputs X6,
check cord set and device.
1037
Fault: pulse outputs Device-Port X7
Cross-fault pulse outputs X7,
check cord set and device.
INFORMATION
"Fault pulse outputs" is reported if there is a cross-fault between
a pulse output Y1 or Y2 and +24 VDC, 0 VDC or between them.
All pulse outputs are switched off if there is a cross-fault to 0 VDC.
INFORMATION
10 s after correcting the fault, the message "Fault outgoing" appears and the fault
can be acknowledged.
Error No. Error message
Help information / Note
Overload fault Power-Supply
Overload Power-Supply at Device-Port
1040
Fault: overload power supply
Device-Port X0
Fuse power supply X0, has tripped
check cord set and device.
1041
Fault: overload power supply
Device-Port X1
Fuse power supply X1, has tripped
check cord set and device.
1042
Fault: overload power supply
Device-Port X2
Fuse power supply X2, has tripped
check cord set and device.
1043
Fault: overload power supply
Device-Port X3
Fuse power supply X3, has tripped
check cord set and device.
1044
Fault: overload power supply
Device-Port X4
Fuse power supply X4, has tripped
check cord set and device.
1045
Fault: overload power supply
Device-Port X5
Fuse power supply X5, has tripped
check cord set and device.
1046
Fault: overload power supply
Device-Port X6
Fuse power supply X6, has tripped
check cord set and device.
1047
Fault: overload power supply
Device-Port X7
Fuse power supply X7, has tripped
check cord set and device.
INFORMATION
"Overload power supply device port" is reported if the
internal auto-resettable fuse has tripped.