68
5 Diagnostic system
Error No. Error message
Help information / Note
Overload fault Digital-Output
Overload Digital-Output at Device-Port
1050
Fault: overload digital output
Device-Port X0
Current limiter digital output X0 activated,
check cord set and device.
1051
Fault: overload digital output
Device-Port X1
Current limiter digital output X1 activated,
check cord set and device.
1052
Fault: overload digital output
Device-Port X2
Current limiter digital output X2 activated,
check cord set and device.
1053
Fault: overload digital output
Device-Port X3
Current limiter digital output X3 activated,
check cord set and device.
1054
Fault: overload digital output
Device-Port X4
Current limiter digital output X4 activated,
check cord set and device.
1055
Fault: overload digital output
Device-Port X5
Current limiter digital output X5 activated,
check cord set and device.
1056
Fault: overload digital output
Device-Port X6
Current limiter digital output X6 activated,
check cord set and device.
1057
Fault: overload digital output
Device-Port X7
Current limiter digital output X7 activated,
check cord set and device.
INFORMATION
"Overload digital output" is reported if the electronic current limitation of the
digital output has tripped.
INFORMATION
If the device port is passivated, the error can no longer be detected and
the message "Fault outgoing" appears“.
Error No. Error message
Help information / Note
Fault Digital-Output
Cross-fault Digital-Output at Device-Port
1060
Fault: digital output Device-Port X0
Cross-fault digital outputs X0,
check cord set and device.
1061
Fault: digital output Device-Port X1
Cross-fault digital outputs X1,
check cord set and device.
1062
Fault: digital output Device-Port X2
Cross-fault digital outputs X2,
check cord set and device.
1063
Fault: digital output Device-Port X3
Cross-fault digital outputs X3,
check cord set and device.
1064
Fault: digital output Device-Port X4
Cross-fault digital outputs X4,
check cord set and device.
1065
Fault: digital output Device-Port X5
Cross-fault digital outputs X5,
check cord set and device.
1066
Fault: digital output Device-Port X6
Cross-fault digital outputs X6,
check cord set and device.
1067
Fault: digital output Device-Port X7
Cross-fault digital outputs X7,
check cord set and device.
INFORMATION
"Fault digital output" is reported if there is a cross-fault from a digital output
to +24 VDC, 0 VDC or an external potential.
INFORMATION
If there is a cross-fault between the digital output and +24V, the master switch
is switched off internally and all digital outputs DO 0 - DO 7 are switched off.
INFORMATION
If the device port is passivated, the error can no longer be detected and