5 Diagnostic system
69
Error No. Error message
Help information / Note
Discrepancy- / Stable time fault
Discrepancy- / Stable time out
1070
Discrepancy / stable time error
Device-Port X0
Monitoring time at X0 exceeded,
check safety guard.
1071
Discrepancy / stable time error
Device-Port X1
Monitoring time at X1 exceeded,
check safety guard.
1072
Discrepancy / stable time error
Device-Port X2
Monitoring time at X2 exceeded,
check safety guard.
1073
Discrepancy / stable time error
Device-Port X3
Monitoring time at X3 exceeded,
check safety guard.
1074
Discrepancy / stable time error
Device-Port X4
Monitoring time at X4 exceeded,
check safety guard.
1075
Discrepancy / stable time error
Device-Port X5
Monitoring time at X5 exceeded,
check safety guard.
1076
Discrepancy / stable time error
Device-Port X6
Monitoring time at X6 exceeded,
check safety guard.
1077
Discrepancy / stable time error
Device-Port X7
Monitoring time at X7 exceeded,
check safety guard.
INFORMATION
A "discrepancy / stability time error" is reported if there is either a temporary or
permanent discrepancy (a difference) between the two input signals,
or the input signals are not stable (refer to Chapter 2.2.3).
This error is also reported if the safeguard has not been closed correctly or
if a temporary single-channel switch-off has occurred.
INFORMATION
Discrepancy errors can also be detected for electronic safety switchgear
(= switched off cross-fault detection) if there is a short circuit to +24 VDC
or 0 VDC at the safety inputs X1/X2 or the pulse outputs Y1/Y2.
Check device connection cables!
INFORMATION
This fault can only be acknowledged after the safety guard has been opened
one time without fault.
For certain types of interlocks, it may be necessary to switch off the operating
voltage of the interlock or of the SFB-PN one time in order to acknowledge the
fault.
Error No. Error message
Help information / Note
Fault FB-Interface
FB-Interface disturbed at Device-Port
1084
Fault: FB-Interface Device-Port X4
No valid response from device at X4,
check cord set and device.
1085
Fault: FB-Interface Device-Port X5
No valid response from device at X5,
check cord set and device.
1086
Fault: FB-Interface Device-Port X6
No valid response from device at X6,
check cord set and device.
1087
Fault: FB-Interface Device-Port X7
No valid response from device at X7,
check cord set and device.
INFORMATION
"Fault FB-Interface" is reported as long as no communication with the
FB-Interface device (BDF200-FB) is possible.