Operating instructions

Safety-monitoring module

SLB 400-C

EN

Number of safety light barriers and height of the light beams:

The number of light beams and the height of the light beams above 

the reference floor are defined by the requirements of the power-driven 

work equipment, the EN ISO 13855 or a risk analysis. The following 

table shows the applicable values to EN ISO 13855 at the time of print-

ing for the height of the light beams above the reference floor and the 

calculation of the safety distance "S":

Number of 

light bar-

riers

Height of the light 

beams above refer-

ence floor in mm

Calculation of  

the safety distance "S"

4

300 / 600 / 900 / 1200 S = (1600 mm/s x T) + 850 mm

3

300 / 700 / 1100

S = (1600 mm/s x T) + 850 mm

2

400 / 900

S = (1600 mm/s x T) + 850 mm

1

750

S = (1600 mm/s x T) + 1200 mm

T =  (response time of the m response time SLB 400-C10-1R) 

in seconds

Deflection

Surfaces, which are arranged parallel to the light beam, can cause a 

deflection. In that case, a obstacle in the light beam will no longer be 

detected. Therefore, a lateral minimum distance for the optical axis 

must be respected and observed with regard to reflecting surfaces or 

obstacles. (Fig. 1a and Fig. 1b). This distance depends on the angle of 

radiation of the light barrier and the distance of transmitter and receiver.

SLB - E

SLB - R

Fig. 1a: safety function inoperative

SLB - E

SLB - R

Fig. 1b:  safety function operational

4.  Electrical connection

The electrical connection may only be carried out by author-

ised personnel in a de-energised condition. The reset button 

must be positioned outside of the hazardous area so that the 

operator has an overview of the hazardous area when actuat-

ing the reset button.

Notes on the wiring diagram

•  For the protection of hazardous areas up to control category 4 / PL e 

to EN ISO 13849-1.

•  Monitoring of one up to four pairs of safety light barriers and the power 

contactor using the SLB 400-C10-1R safety-monitoring module.

•  Use a micro-fuse (2 A quick blow) to protect the relay output contacts.

• Terminal configuration: max. 2 wired.

4.1  Wiring example

L1

K4

K5

+24 VDC

0 V

0 V

N

3 ~

M

X2

X1

A1

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

X3

X4

X7

X5

X6

X8

13

23

33

41

A2

0V

SLB-E

SLB-E

SLB-E

SLB-R

SLB-R

SLB-R

SLB-R

SLB-E

T3

Q3 T4

Q4

PM

INDIC.

U    OUT

U    OUT

B

B

Y1

Y2

-

-

+

+

X9

X10 X11 X12 X13 X14

14

24

34

42

24V T1

T2

Q1

Q2 RESTART CONT.M

Made in Germany

RESTART

RELAY

J

Transmitter SLB-E

Receiver SLB-R

1 (BN):   +UB

1 (BN):   +UB

2 (WH):   Test

2 (WH):   Qp (pollution)

3 (BU):   0V

3 (BU):   0V

4 (BK):   not connected

4 (BK):   Q

Inductive loads must be suppressed by means of a suitable 

circuit (use contact protection parallel to the load).

The outputs Y1 and Y2 nor the signalling contacts must be 

integrated in the safety circuit.

To avoid any mutual interference, every transmitter / receiver 

must be connected by means of a separate cable. If multiple 

light barriers are connected to a cable, a cable with individual 

conductor shielding mut be used.

Operation with less than four pairs of safety light barriers

If less than four pairs of safety light barriers are connected, the termi-

nals of the non-connected light barriers (X1/X2, X3/X4, X9/X10, X11/

X12) must be bridged. Upon delivery, a bridge is installed between the 

terminals X3/X4, X9/X10, X11/X12.

Operation with start/restart interlock (manual start)

The operating mode with start/restart interlock (start/restart) is set 

through DIP switches (refer to the chapter Device settings).

The command device (NO contact) is connected to the terminals X5 

and X6. After the interruption of a safety light barrier, the command 

device must be actuated for at least 250 ms and 5 s at the most and 

then be released. The indication disappears and the enabling paths are 

enabled. If the command device is not actuated after the operating volt-

age has been switched on, the enabling paths remain open.