Operating instructions

Safety light barriers

SLB240

EN

5.2  Maintenance

Do not use the AOPD before the next inspection has been 

completed An incorrect installation can lead to serious and 

mortal injuries

Conditions

For safety reasons, all inspection results must be archived The 

operating principle of the AOPD and the machine must be known in 

order to be able to conduct an inspection If the fitter, the planning 

technician and the operator are different persons, please make sure 

that the user has the necessary information at his disposal to be able 

conduct the maintenance

5.3  Regular check

A regular visual inspection and functional test, including the following 

steps, is recommended:

1  The component does not have any visible damages

2  The optics cover is not scratched or soiled

3  Hazardous machinery parts can only be accessed by passing 

through the protection zone of the AOPD

4  The staff remains within the detection area, when works are 

conducted on hazardous machinery parts

5  The safety distance of the application exceeds the mathematically 

calculated one

Operate the machine and check whether the hazardous movement 

stops under the hereafter-mentioned circumstances.

1  Hazardous machine parts do not move when the protection field is 

interrupted

2  The hazardous machine movement is immediately stopped, when 

the protection field is interrupted with the test rod immediately before 

the transmitter, immediately before the receiver and in the middle 

between the transmitter and the receiver

3  No hazardous machine movement when the test rod is within the 

protection field

4  The hazardous machine movement comes to standstill, when the 

voltage supply of the AOPD is switched off

5.4  Half-yearly inspection

The following items must be checked every six months or when a 

machine setting is changed

1  Machine stops or does not inhibit any safety function

2  No machine modification or connection change, which affects the 

safety system, has taken place

3  The outputs of the AOPD are correctly connected to the machine

4  The total response time of the machine does not exceed the 

response time calculated during the first putting into operation

5  The cables, the connectors, the caps and the mounting angles are in 

perfect condition

5.5  Cleaning

If the optics cover of the sensors is extremely soiled, the OSSD outputs 

can be disabled Clean with a clean, soft cloth with low pressure

The use of agressive, abrasive or scratching cleaning agents, which 

could attack the surface, is prohibited

4.2  Connector configuration Receiver, Transmitter & Cable

TRANSMITTER

Connector  

M12, 4-pole

PIN

Designation

Description

3

2

1

4

1

+24 V

Power supply

2

Test

Test input

3

0 V

Power supply

4

NC

Unassigned

Connector female  

M12, 4-pole

3

2

1

4

RECEIVER

Connector  

M12, 5-pole

PIN

Designation

Description

3

2

5

1

4

1

+24 V

Power supply

2

OSSD1

Safety output 1

3

0 V

Power supply

4

OSSD2

Safety output 2

5

Restart interlock 
(manual reset)

Authorisation / restart

Connector female  

M12, 5-pole

3

2

5

1

4

5.  Set-up and maintenance

5.1  Check before start-up

Prior to start-up, the following items must be checked by the 

responsible person

Wiring check prior to start-up

1  The voltage supply is a 24V direct current power supply (see 

technical specifications), which meets the CE Directives, Low  

Voltage Directives A power downtime of 20 ms must be bridged

2  Presence of a voltage supply with correct polarity at the AOPD

3  The connecting cable of the transmitter is correctly connected to the 

transmitter and the connecting cable of the receiver correctly to the 

receiver

4  The double insulation between the output and an external potential 

is assured

5  The outputs OSSD1 and OSSD2 are not connected to +24 VDC

6  The connected switching elements (load) are not connected  

to +24 VDC

7  If two or more AOPDs are used within close range compared to each 

other, an alternating arrangement must be observed Any mutual 

interference of the systems must be prevented

Switch the AOPD on and check the operation in the following way:

The component performs a system test during approx 2 seconds after 

the operating voltage has been switched on The outputs are then 

enabled if the protection field is not interrupted The status indication at 

the receiver is on

In case of incorrect functionality, please follow the instructions 

listed in the chapter Fault diagnostic

Summary of Contents for SLB240

Page 1: ...warning notice could lead to physical injury and or damage to the machine Content 1 About this document 1 1 Function 1 1 2 Target group authorised qualified personnel 1 1 3 Explanation of the symbols...

Page 2: ...are strictly forbidden the manufacturer shall accept no liability for damages resulting from such invasive work arbitrary repairs conversions and or modifications to the device 2 Product description 2...

Page 3: ...nal low Green ON state protection zone uninterrupted OSSD signal high 2 8 2 Protection mode with restart interlock In the operating mode restart interlock the safety switching outputs OSSD remain in t...

Page 4: ...y relevant faults are detected within the reaction time and cause the outputs to be put in the OFF state and an error code is indicated 3 Mounting 3 1 General conditions The following guidelines are p...

Page 5: ...m Prevent the possibility of reaching through between two beams Prevent the possibility of climbing through between two beams Safety distance to the hazardous area S Hazardous point Transmitter Receiv...

Page 6: ...procal interference The response time of the system changes with the selected beam coding The safety distance must be adapted accordingly See section on reaction time When the system starts the integr...

Page 7: ...anual reset Adapter cable for parameter setting Item No Designation Description Length 103013625 KA 0977 Pushbutton with command device 1x male connector M12 5 pole 2x female connector M12 5 pole 3 m...

Page 8: ...achine does not exceed the response time calculated during the first putting into operation 5 The cables the connectors the caps and the mounting angles are in perfect condition 5 5 Cleaning If the op...

Page 9: ...interlock is active SLB waiting for enabling signal Red Status of OSSD safety switch outputs is OFF protection field is not clear Red Alternating OFF pulses signalise the fault status see section on...

Page 10: ...ompilation of the technical documentation Oliver Wacker M ddinghofe 30 42279 Wuppertal K A Schmersal GmbH Co KG M ddinghofe 30 42279 Wuppertal Deutschland Telefon 49 202 6474 0 Telefax 49 202 6474 100...

Reviews: