background image

4

Operating instructions

Safety light barriers

SLB440

SLB450

EN

2.8.2 Protection mode with restart interlock

In the operating mode restart interlock, the safety switching outputs 

(OSSD) remain in the OFF condition after the power supply is applied 

or after the protection zone has been interrupted

The AOPD switches the OSSDs to the ON state once the restart input 

signal impulse is applied with a duration of 100 ms < T < 1500 ms using 

a command device (push button)

The receiver indicates the readiness for authorized operation with a 

yellow signal on the end cap If the protection zone is interrupted, the 

signal will indicate red

The AOPD changes to alignment aid mode if the enabling 

button is pressed for at least 2 seconds when the operating 

voltage is applied, see chapter Alignment aid

The command device (enabling button) must be installed 

outside of the hazardous area The hazardous zone must 

be easily visible to the user

Display

Diagnostic lamp Status

Red

OFF state (protection zone interrupted,  
OSSD signal low)

Green

ON state (OSSD signal high)

Yellow

Restart interlock is active,  
SLB waiting for enabling signal

2.8.3 Parameter setting

In parameterisation mode, individual adaptation of the operating 

parameters for transmitter and receiver can be carried out

Possible options are:

No. Option

Description

P1

active / not active

Beam coding 1 (response time 10 ms)

P2

active / not active

Beam coding 2 (response time 14 ms)

P3

active / not active

Beam coding 3 (response time 18 ms)

P4

active / not active

Beam coding 4 (response time 25 ms)

P5

active / not active

Beam coding 5 (response time 7 ms)

P6

active / not active

active = restart interlock
not active= automatic mode

P7

active / not active

Heater regulation:
Only on SLB450 with integrated heater

The beam coding 5 may only be used if no other SLBs  

are operated in parallel

The response time of the system changes with the 

selected beam coding The safety distance must be 

adapted accordingly See section on reaction time

Parameter setting with adapter cable KA-0977

•  Switch the supply voltage off

•  Connect adapter cable KA-0977 to the device

•  Press and hold the integrated button and switch the supply voltage on 

The button can be released as soon as the indicator of the receiver 

changes from red to yellow and the indicator of the transmitter 

changes from blue to yellow

•  The AOPD is now in setup mode The signal strength is displayed  

on the receiver through impulses or steady illumination of the  

yellow LEDs

•  To change to parameterisation, the button must be pressed briefly  

(100 ms < T < 1500 ms)

•  The status of parameter P1 is now indicated The signal lamp lights up 

once in cyan (parameter is active) or magenta (parameter is not active)

•  Press the button briefly to change to the next parameter The number 

of light impulses indicates the parameter number, the colour indicates 

the parameter status (cyan = active, magenta = not active)

•  Press and hold the button (25 seconds < T < 6 seconds) and the 

status of the current parameter changes from ACTIVE to NOT ACTIVE 

or from NOT ACTIVE to ACTIVE and is saved While the button is 

pressed, the indicator changes after 15 seconds to a static indication 

of the current parameter setting Pressing and holding the button 

longer T > 25 seconds indicates the colour of the new status The 

button can now be released to save If the button is pressed and held 

for longer than 6 seconds, the indicator goes out and the change is 

not accepted

•  To exit parameterisation mode, switch the supply voltage off and 

restore the original wiring

Transmitters and receivers can be configured simultaneously 

with adapter cable KA-0977

Parameter P6 restart interlock only acts on the receiver  

The parameter is only indicated on the transmitter

Parameter setting without adapter cable KA-0977

As an alternative to the adapter cable, a button can be connected as 

follows:

Wiring configuration  

Transmitter

Wiring configuration  

Receiver

+24VDC

2

3

4

1

   0

 

VDC

Range 1

Range 2

0 VDC

+24 VDC

2

4

3

1

5

+24VDC

   0

 

VDC

OSSD 2

Authorised operation

+24 VDC

0 VDC

OSSD 1

2.8.4 Self-test

The AOPD carries out a self-test within 2 seconds after the power 

supply is applied In the event of a fault, the AOPD is locked in the OFF 

state and reports the status (see section on fault diagnosis)

After a successful self-test the AOPD switches to the ON state if the 

protection zone is clear (automatic operating mode)

During operation, the system executes a cyclic self-test Safety-relevant 

faults are detected within the reaction time and cause the outputs to be 

put in the OFF state and an error code is indicated

Summary of Contents for SLB440

Page 1: ...d lead to physical injury and or damage to the machine Content 1 About this document 1 1 Function 1 1 2 Target group authorised qualified personnel 1 1 3 Explanation of the symbols used 1 1 4 Appropri...

Page 2: ...ents cannot be excluded when safety device is used The relevant requirements of the standards EN ISO 13855 EN ISO 13857 must be observed Only if the information described in this operating instruction...

Page 3: ...ailure OSSD leakage current The downstream control element must recognise this state as LOW A safety PLC must detect this state 4 The load inductivity generates an induced voltage during the switch of...

Page 4: ...e released as soon as the indicator of the receiver changes from red to yellow and the indicator of the transmitter changes from blue to yellow The AOPD is now in setup mode The signal strength is dis...

Page 5: ...light impulses The better the alignment the higher the frequency of the light pulses The alignment is optimal when the light pulses switch over to continuous light If there is no optical synchronisati...

Page 6: ...fety distance between the safety light barrier and the hazardous point must always be respected and observed If a person reaches the hazardous point before the hazardous movement has come to a standst...

Page 7: ...at risk if systems are operated with reciprocal interference The response time of the system changes with the selected beam coding The safety distance must be adapted accordingly See section on reacti...

Page 8: ...5 m For use in the operating mode Restart Interlock manual reset Adapter cable for parameter setting Item No Designation Description Length 103013625 KA 0977 Pushbutton with command device 1x male con...

Page 9: ...e 1 BK Range 2 WH OSSD 2 BK 0 VDC BU 24 VDC BN Release restart GY 24 VDC BN 0 VDC BU OSSD 1 WH Earth connection S 1 K1 K2 5 1 3 2 4 E1 2 4 1 3 Protective mode Automatic active Delivery state Command d...

Page 10: ...d The operating principle of the AOPD and the machine must be known in order to be able to conduct an inspection If the fitter the planning technician and the operator are different persons please mak...

Page 11: ...ver the indicator is delayed until there is no change in the ON state or OFF state of the OSSDs for 5 seconds Only SLB450 transmitter If the transmitter is configured for alternative range an addition...

Page 12: ...n of the technical documentation Oliver Wacker M ddinghofe 30 42279 Wuppertal K A Schmersal GmbH Co KG M ddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Tele...

Reviews: