background image

3

EN

SLC 430

Operating instructions

Safety light curtain

LED indications sensor R:

 

OSSD ON, OSSD OFF, restart interlock  

(manual reset) enabling

Sensor connection:

 

M8 x 1, 4-pole shielded female connector; 

cable length 5m

Safety-monitoring module connection:

 

Removable screw terminal 

block

Ambient temperature:

 

0° C ... +50° C

Storage temperature:

 

−10° C ... +70° C

Synchronisation:

 

RS 485 BUS

Protection class:

 

IP65 (IEC 60529)

Resistance to vibrations:

 

10 … 55 Hz to IEC 60068-2-6

Resistance to shock:

 

10 g; 16 ms; to IEC 60068-2-29

Fuses:

Power supply:

 

F1: 1.6 A / 250 V T

Output contacts:

 

F5, F6: 4.0 A / 250 V T

Signalling output:

 

F7: 4.0 A / 250 V T

Year of construction:

 

as of 2010 version 1.0

2.6  Safety classification

Standards:

 

EN ISO 13849-1, EN 62061

PL:

 

up to e

Control category:

 

up to 4

PFH value:

 

1.26 x 10

-8

 /h

SIL:

 

up to 3

Service life:

 

20 years

2.7  Functions

The system consists of 2 components, the E/R sensors and the NSR-

0605 safety-monitoring module.

The connection between these components is realised through a 4-pole 

female connector for the sensor connection. The transmitter and recei-

ver units are supplied with direct-current voltage through the NSR-0605 

safety-monitoring module. All system components are connected to the 

safety-monitoring module.

The protection field is generated between both sensors E and R, which 

each represent a transmitter and a receiver unit. The safety-monitoring 

module obtains the signals of the transmitter and receiver units through 

a RS-485 BUS connection and makes the corresponding status 

available at the output through two safety relays. To trigger a switch-off 

command, covering just one light beam will suffice.

The safety light curtain is self-monitoring, i.e. for every fault occuring 

in the system either during the self-test or covered by an external test, 

the OSSD outputs are disabled. As long as the fault remains active, the 

system will remain locked in OFF condition. This locked situation is not 

cancelled by switching-off and back on the supply voltage either.

The system has the following features:

•  Protective mode

•  Restart interlock (manual reset)

•  Contactor check

2.7.1 Protective mode / standard operation

The protective mode switches the OSSD outputs to ON state (protec-

tion field not interrupted), without external release of a switching device. 

This type of protection generates an automatic restart of the machine if 

the protection field is not interrupted.

This operating mode may only be chosen in conjunction with 

the restart interlock (manual reset) of the machine.

This operating mode must not be chosen, when persons can 

step behind the protection field.

2.7.2 Restart interlock (manual reset) / hold function

In this way, the system is kept in a locked condition after a protection 

field interruption, after switch-on or after power off (OSSD's OFF state). 

The locking condition will only be cancelled after the protection field is 

enabled and an external command device has been actuated. To switch 

between normal and hold operation (restart interlock), a slide switch on 

the control unit is used.

The command devices (enabling button) must be installed 

outside of the hazardous area. The operator must have a 

clear view on the hazardous area when actuating the enab-

ling button.

2.7.3 Contactor control (EDM)

The contactor control monitors the controlled switching elements 

(auxiliary contacts of the contactors) of both outputs. This monitoring 

is realised after each interruption of the protection field and prior to 

the restart (enabling) of the outputs. In this way, malfunctions of the 

relays are detected, e.g. contact welding or contact spring breakage. 

If the light curtain detects a malfunction of the switching elements, the 

outputs are locked. (s. Electrical connection)

2.7.4 Testing / external test

The system can trigger a test cycle by means of the external test input. 

By applying a signal (+ 24 VDC) at the test output, a complete self-test 

is executed. The outputs change to OFF state and are re-enabled after 

1.5 s if no fault is detected.

Regardless of the activation of the external test input, a self-test is 

cyclically executed within the permissible triggering time of the system. 

The condition at the output relays does not change. The system is only 

switched off when a fault is detected.

2.7.5 Signalling output / low-voltage safety output

The safety-monitoring module has a potential-free changeover contact 

for the connection of a signal lamp. In this way, the signal conditions 

OSSD ON and OSSD OFF can be visualised on the machine by means 

of an indicator light. The signal lamp can be operated with 12V, 24V or 

42V.

3.  Mounting

3.1  General conditions

The following guidelines are provided as a preventive warning notice 

to ensure  safe and appropriate handling. These guidelines are an 

essential part of the safety instructions and therefore must always be 

observed and respected.

•  The SLC must not be used on machines, which can be 

stopped electrically in case of emergency.

•  The safety distance between the SLC and a hazardous ma-

chine movement must always be observed and respected.

•  Additional mechanical safety guards must be installed so 

that the operator has to pass by the protection field to reach 

the hazardous machine parts.

•  The SLC must be installed so that the personnel always 

must be within the detection zone when operating the ma-

chine. An incorrect installation can lead to serious injuries.

•  Never connect the outputs to +24VDC. If the outputs are 

wired to +24VDC, they are in ON state, as a result of which 

they are unable to stop a hazardous situation occuring on 

the application/machine.

•  The safety inspections must be conducted regularly.

•  The SLC must not be exposed to inflammable or explosive 

gasses.

•  The connecting cables must be connected in accordance 

with the installation instructions.

•  The fixing screws of the end caps of the mounting angle 

must be firmly tightened.

Summary of Contents for SLC 430

Page 1: ...ith this warning notice could lead to physical injury and or damage to the machine 1 4 Appropriate use The products described in these operating instructions are developed to execute safety related fu...

Page 2: ...field heights in mm available lengths 0236 0460 0684 0908 1132 1356 1580 1804 Only if the information described in this operating instructions manual are realised correctly the safety function and th...

Page 3: ...only be cancelled after the protection field is enabled and an external command device has been actuated To switch between normal and hold operation restart interlock a slide switch on the control uni...

Page 4: ...ad and foot positions of both edges swapped The connector plugs are located at the head end of both sensors and therefore must point in the same direction the common direction however is not impor tan...

Page 5: ...lculation examples are related to the vertical set up refer to drawing of the light curtain with regard to the hazardous point Please observe the applicable harmonised EN standards and possible applic...

Page 6: ...460 30 RF 460 691 5 0 4 SLC 430 E R0684 30 RF 684 915 5 0 55 SLC 430 E R0908 30 RF 908 1139 5 0 65 SLC 430 E R1132 30 RF 1132 1363 5 0 8 SLC 430 E R1356 30 RF 1356 1587 5 0 9 SLC 430 E R1580 30 RF 158...

Page 7: ...carrying capacity is 4 A 250 VAC Both safety outputs must not be wired in series They must be wired 2 channel to the machi ne control In addition to both main outputs output 1 output 2 a signalling ou...

Page 8: ...on It must be impossible to restart the hazardous parts before the BWS has completely returned to its normal state and the machine control elements have been reactuated 3 Check the machine to ensure t...

Page 9: ...ansmitter ON orange Sensor E active 6 2 Optical and acoustic signals in the control unit The control unit includes an acoustic signal generator buzzer as well as multiple LED s The LED s n 1 2 and 3 g...

Page 10: ...he fuse of the supply voltage input Check fuse F1 Protection field clear but no enabling Normal operation LED 5 red emits every 3 seconds the following flash impulses Permanent flashing Synchronisatio...

Page 11: ...on authorised for the compilation of the tech nical documentation Ulrich Loss M ddinghofe 30 42279 Wuppertal Notified body for the prototype test T V Nord Cert GmbH Langemarckstr 20 45141 Essen ID n 0...

Page 12: ...Safety Control GmbH Am Industriepark 33 D 84453 M hldorf Inn Telefon 49 0 86 31 187 9 60 Telefax 49 0 86 31 187 9 61 E Mail info safetycontrol com...

Reviews: