5

SLG440

Operating instructions
Safety light grids

EN

2.8.4 Blanking of moving objects

The SLG440 can blank movable objects in the protection field

4
3
2

1

R1

E1

The moving blanking range is authorised for individual beams in case of 
obstacles, taking the protective function into account

The function enables an arbitrary floating blanking of partial areas in the 
protection field  The first beam, which is located immediately behind 
the diagnostic window, cannot be blanked

This function allows for an interruption of maximum 1 light beam 
without the outputs being disabled in case of material movement in the 
protection field, eg ejection of material or process-controlled material 
movement

The operating mode is only available, when the parameter setting P 3 is 
activated See chapter Parameter setting

•  The variable blanking of one beam is not authorised with 

 

the 2-beam SLG440!

•  The blanking of one beam at the most in the SLG440 

3-beam version or the SLG440 4-beam version is 
 authorised, provided that the protective function is taken  
into account

•  The restart interlock (manual reset) function of the safety 

light grid or the machine must be activated

•  The protection field must be checked with a test rod by a 

qualified person after the configuraiton

•  The standard IEC/TS 62046 includes information, which 

describes possibly required additional measures to prevent 
a person from reaching a hazard through the beam blanking 
of a protection field

2.8.5 Contactor control (EDM)

The contactor control monitors the controlled switching elements 
(auxiliary contacts of the contactors) of both outputs This monitoring 
is realised after each interruption of the protection field and prior to the 
restart (enabling) of the outputs In this way, malfunctions of the contac-
tors are detected, eg contact welding or contact spring breakage If 
the light curtain detects a malfunction of the switching elements, the 
outputs are locked
After elimination of the error, a power reset is required

The contactor control is not activated upon delivery The 
function is activated in parameter setting mode (P 4)

Connection EDM
Wiring of the receiver

-  Kn1, Kn2 = auxiliary contact  

of the last switching relay

+24VDC

Kn1

Pin 8

Kn2

 The auxiliary contacts must only be connected, when the 
function is activated!

2.8.6 Rotating the display through 180 degrees

The orientation of the 7 segment display can be rotated through 180 
degrees via the software option This ensures that the display remains 
readable in rotated mounting positions of the AOPD

Parameter 

P 7 –

Display normal orientation

Parameter 

P 7 A

Display rotated

2.9  Self-test

The system performs a complete self-test and safety test within 2 sec-
onds after the operating voltage has been switched on If the protection 
field is free, the system switches to the ON condition (automatic mode) 
In case of an error, the outputs at the receiver do not switch to the ON 
state An error message is emitted in the form of an error code For 
more information, refer to chapter Fault diagnosis

During operation, the system executes a cyclic self-test  Safety-rele-
vant faults are detected within the reaction time and cause the outputs 
to be switched off and an error code to be emitted

2.10  Beam coding A

The preset beam coding of the safety light grid must be adjusted, when 
systems operating in each other's vicinity and a set-up as shown in the 
image below (no interference) is impossible When supplied, the beam 
coding A is 

not active

 A receiver with activated beam coding A can dis-

tinguish the beams of the transmitter with the same beam coding, which 
are destined to this particular receiver, from foreign beams

If adjacent systems are operated without beam coding A, the user is at 
risk

E

E

R

R

E

R

R

E

No interference

Interference:  

beam coding A required!

•  The beam coding A avoids mutual interference of adjacent systems.

•  The beam coding A is permanently shown by the transmitter and the 

receiver by means of flashing LED's (refer to LED status information)

•  The beam coding A must be set for 

each sensor

 (receiver and  

transmitter) individually

•  The function at the receiver is activated in parameter setting 

 

mode (P 6)

Summary of Contents for SLG440

Page 1: ...About this document 1 1 Function 1 1 2 Target group authorised qualiied personnel 1 1 3 Explanation of the symbols used 1 1 4 Appropriate use 2 1 5 General safety instructions 2 1 6 Warning about mis...

Page 2: ...liability for damages and malfunctions resulting from defective mounting or failure to comply with this operating instructions manual The manufacturer shall accept no liability for damages result ing...

Page 3: ...restart interlock restart interlock 2 Input voltage HIGH active 11 30 V Input voltage LOW inactive 0 2 0 V Input current HIGH 3 10 mA Input current LOW 0 3 mA Functions automatic mode restart interloc...

Page 4: ...tputs OSSD s ON state after switch on of the operating volt age or an interruption of the protection field The system switches the outputs only to ON state when an external command device restart butt...

Page 5: ...is required The contactor control is not activated upon delivery The function is activated in parameter setting mode P 4 Connection EDM Wiring of the receiver Kn1 Kn2 auxiliary contact of the last sw...

Page 6: ...signalled in the following way 7 segment display LED OSSD ON red active LED OSSD OFF green active Parameter setting 1 When S1 is briely pressed the display shows repeatedly Parameter P 1 not active f...

Page 7: ...lication machine The safety inspections must be conducted regularly The SLG must not be exposed to inflammable or explosive gasses The connecting cables must be connected in accordance with the instal...

Page 8: ...eceive signal OK Beam b no receive signal Beam a and beam b receive signals OK Indication basic setting The signal strength is displayed per beam with two segments for the first a and the last b beam...

Page 9: ...tion from which the hazardous area is accessed To calculate the minimum distances of the safety guards with regards to the hazardous point the EN ISO 13855 and EN ISO 13857 must be observed If an over...

Page 10: ...0900 04 XX 300 1024 1043 258 5 217 5 L1 Mounting distance mm between floor and slotted hole centre short end cap L2 Mounting distance mm between floor and slotted hole centre diagnostic window Overal...

Page 11: ...reen outputs H signal 24V Red outputs L signal 0V Yellow setting mode restart interlock manual reset 24 5 12 5 15 0 1 The integrated status indication does not change the mounting dimen sion B or the...

Page 12: ...N 0 VDC BU Earth connection Restart interlock manual reset bridge 1 By bridging restart 2 pin 5 and DOUT pin 6 the restart interlock manual reset is activated Connect S1 to Pin1 Protective mode Automa...

Page 13: ...power supply see techni cal specifications which meets the CE Directives Low Voltage Directives A power downtime of 20 ms must be bridged 2 Presence of a voltage supply with correct polarity at the S...

Page 14: ...ring the first putting into operation 5 The cables the connectors the caps and the mounting angles are in perfect condition 5 5 Cleaning If the optics cover of the sensors is extremely soiled the OSSD...

Page 15: ...blanking area s of fixed or floating objects with the selected parameter setting fault elimination repeat configuration in the parameter setting possibly adjust P 1 P 2 P 3 Configuration error in para...

Page 16: ...13144608 Person authorized for the compilation of the technical documentation Oliver Wacker M ddinghofe 30 42279 Wuppertal K A Schmersal GmbH Co KG M ddinghofe 30 D 42279 Wuppertal Postfach 24 02 63...