background image

6

Operating instructions
Safety light grids

SLG440

EN

Transmitter parameter setting

Wiring of the transmitter

-  Jumper connection  

pin 1 with pin 2

-  Jumper connection  

pin 3 with pin 4

Pin 1

Pin 2

+ 24V/DC

Pin 3

Pin 4

0V/DC

The response time of the system is increased when beam 
coding A is used To this end, the safety distance must be 
adjusted Refer to chapter: Response time

2.11 Parameter setting

The parameter setting of the SLG440 enables the individual adjustment 
of the desired functionality to the application

Parameter display (7-segment display)

A  = parameter active
-  = parameter not active

S.

 = save the current configuration

C.

 =  delete the current configuration, new configuration = factory setting

n  =  unavailable (unauthorised setting, refer to Parameter setting infor-

mation)

d.

 = diagnostic/setting mode

Parameter selection

Selection, change and acceptance of the parameters by means of the 
command device pushbutton S1:
- Switch to parameter setting Px   briefly press the button  

01 … 15 sec

- Change parameter setting Px 

 press button 25 … 6 sec

- Save 

S.

 / Factory setting 

C.

 

 press button 25 … 6 sec

Procedure

1)  For the parameter setting, the receiver must be isolated from the 

operating voltage  In de-energised condition, the following jumper 
connection and the pushbutton S1 must be connected

Freigabe WA

DOUT

EDM

Pin 8

Pin 6

Pin 1

S 1

+ 24 VDC

Release 

 

restart interlock

Wiring of the receiver

•  Jumper connection from DOUT (Pin 6) to EDM (Pin 8)

•  Connection of the command device pushbutton S1 (+24 VDC) on 

 

Pin 1 (restart interlock)

•  Possible jumper connections from Pin 5 to Pin 6 or Pin 1 to Pin 6 must 

be removed If the EDM function was activated, the auxiliary contact 
of Pin 8 must be removed

2)  The receiver switches to parameter setting mode when the operating 

voltage is switched on

The operating status is signalled in the following way

7- segment display

LED OSSD ON (red) active

LED OSSD OFF (green) active

Parameter setting

1)  When S1 is briely pressed, the display shows 

repeatedly 

 

 - (Parameter P 1 not active, factory setting)

2)  Select the desired parameter by means of command device S1 

(briefly press the button)

3)  Select the desired parameter by means of the command device 

(press the button for a long time) 
1 Push button (approx 25 seconds) 

 

-

 flashes (parameter not active) 

2 Enable button when 

 

A

 static (parameter active)

4)  Save the new configuration with the parameter Save 

S.

 (push the 

button for a long)  
1 Actuate button (approx 25 seconds) 

 

S.

 lashes

 

2 Enable button when 

 

S.

 static 

3   Automatic  restart 

 "segment circulation" 

then 

P

 is displayed (saving operation successful)

If no restart takes place (

S.

), the saving operation has not been 

 successful (ie the parameter changes have not been saved)
The procedure 4 (1 to 3) must be repeated

All parameters can be reset to the factory setting using parameter 

C.

 

(clear/delete)  
1) Press the button approx 25 seconds) 

 

C.

 flashes 

2) Enable the button when 

 

C.

 static 

3)   Automatic  restart 

 "Segment circulation", then 

P

 is displayed  

(all parameters have been deleted)

Return to normal operating mode

1  Switch off the operating voltage at the receiver

2.  Remove jumper connection at the receiver DOUT (Pin 6) and 

 

EDM (Pin 8)

3  Select the desired operating mode (jumper connections)
4  Switch operating voltage on

Adapter cable for parameter setting

If the wiring for the parameter setting of the receiver is not acces-
sible, the KA-0974 adapter cable can be used as an alternative The 
adapter cable is connected between the connecting cable and the 
cable connector of the receive The parameters are set by means of the 
command device (pushbutton), as described in the parameter setting 
After the parameters have been set, the KA-0974 is removed and the 
connecting cable is connected to the receiver

1

2

Key

1 = Connecting cable Receiver
2 =  Command device pushbutton 

for release

Summary of Contents for SLG440

Page 1: ...About this document 1 1 Function 1 1 2 Target group authorised qualiied personnel 1 1 3 Explanation of the symbols used 1 1 4 Appropriate use 2 1 5 General safety instructions 2 1 6 Warning about mis...

Page 2: ...liability for damages and malfunctions resulting from defective mounting or failure to comply with this operating instructions manual The manufacturer shall accept no liability for damages result ing...

Page 3: ...restart interlock restart interlock 2 Input voltage HIGH active 11 30 V Input voltage LOW inactive 0 2 0 V Input current HIGH 3 10 mA Input current LOW 0 3 mA Functions automatic mode restart interloc...

Page 4: ...tputs OSSD s ON state after switch on of the operating volt age or an interruption of the protection field The system switches the outputs only to ON state when an external command device restart butt...

Page 5: ...is required The contactor control is not activated upon delivery The function is activated in parameter setting mode P 4 Connection EDM Wiring of the receiver Kn1 Kn2 auxiliary contact of the last sw...

Page 6: ...signalled in the following way 7 segment display LED OSSD ON red active LED OSSD OFF green active Parameter setting 1 When S1 is briely pressed the display shows repeatedly Parameter P 1 not active f...

Page 7: ...lication machine The safety inspections must be conducted regularly The SLG must not be exposed to inflammable or explosive gasses The connecting cables must be connected in accordance with the instal...

Page 8: ...eceive signal OK Beam b no receive signal Beam a and beam b receive signals OK Indication basic setting The signal strength is displayed per beam with two segments for the first a and the last b beam...

Page 9: ...tion from which the hazardous area is accessed To calculate the minimum distances of the safety guards with regards to the hazardous point the EN ISO 13855 and EN ISO 13857 must be observed If an over...

Page 10: ...0900 04 XX 300 1024 1043 258 5 217 5 L1 Mounting distance mm between floor and slotted hole centre short end cap L2 Mounting distance mm between floor and slotted hole centre diagnostic window Overal...

Page 11: ...reen outputs H signal 24V Red outputs L signal 0V Yellow setting mode restart interlock manual reset 24 5 12 5 15 0 1 The integrated status indication does not change the mounting dimen sion B or the...

Page 12: ...N 0 VDC BU Earth connection Restart interlock manual reset bridge 1 By bridging restart 2 pin 5 and DOUT pin 6 the restart interlock manual reset is activated Connect S1 to Pin1 Protective mode Automa...

Page 13: ...power supply see techni cal specifications which meets the CE Directives Low Voltage Directives A power downtime of 20 ms must be bridged 2 Presence of a voltage supply with correct polarity at the S...

Page 14: ...ring the first putting into operation 5 The cables the connectors the caps and the mounting angles are in perfect condition 5 5 Cleaning If the optics cover of the sensors is extremely soiled the OSSD...

Page 15: ...blanking area s of fixed or floating objects with the selected parameter setting fault elimination repeat configuration in the parameter setting possibly adjust P 1 P 2 P 3 Configuration error in para...

Page 16: ...13144608 Person authorized for the compilation of the technical documentation Oliver Wacker M ddinghofe 30 42279 Wuppertal K A Schmersal GmbH Co KG M ddinghofe 30 D 42279 Wuppertal Postfach 24 02 63...

Reviews: