background image

7

SLG440

Operating instructions
Safety light grids

EN

Table Parameter setting

No. Parameter

Status

Note

P 1

not available

n

not available

P 2

not available

n

not available

P 3

Floating blanking 1 

light beam

– = not active

1 = 1 beam

Blanking of 

one 

beam,  

only for resolution 300 mm 

and 400 mm 

P 4

Contactor control/ 

EDM

– = not active

A = Active

The auxiliary (NC) contacts 

are monitored

P 5

Double acknow-

ledgement with com-

mand device restart 

interlock N° 2

– = not active

A = Active

Operating mode "Protective 

mode with double reset" 

restart n° 2"

P 6

Beam coding A 

(alternative)

– = not active

A = Active

Activating upon mutual 

interference of identical 

systems

P 7

Rotating the display 

through 180 degrees

– = not active

A = Active

The orientation of the  

7 segment display can be 

turned through 180 degrees

S.

Save

S

Press button S1 to  

save changes  

(25 …60 sec) 

C.

Clear/delete

C

Press button S1 to  

save factory setting  

(25 …60 sec)

d.

Diagnostic/ 

setting mode

d

Switch to setting mode

P 1 and P 2 - not available!
P 6 - Beam coding A must also be set at the transmitter,  
refer to chapter Beam coding A

3.  Mounting

3.1  General conditions

The following guidelines are provided as preventive warning notices 
to ensure a safe and appropriate handling  These guidelines are an 
essential part of the safety instructions and therefore must always be 
observed and respected

• 

 The SLG must not be used on machines, which can be 
stopped electrically in case of emergency

• 

 The safety distance between the SLG and a hazardous ma-
chine movement must always be observed and respected

• 

 Additional mechanical safety guards must be installed so 
that the operator has to pass by the protection field to reach 
the hazardous machine parts

• 

 The SLG must be installed so that the personnel always 
must be within the detection zone when operating the ma-
chine An incorrect installation can lead to serious injuries

• 

 Never connect the outputs to +24VDC If the outputs are 
wired to +24VDC, they are in ON state, as a result of which 
they are unable to stop a hazardous situation occurring on 
the application/machine

• 

 The safety inspections must be conducted regularly

• 

 The SLG must not be exposed to inflammable or explosive 
gasses

• 

 The connecting cables must be connected in accordance 
with the installation instructions

• 

 The fixing screws of the end caps and the mounting angle 
must be firmly tightened

3.2  Protection field and approach

The protection field of the SLG consists only of the individual beams 
with a distance of 300, 400 or 500 mm Additional protective devices 
must ensure that hazardous machine components can only be reached 
after passing through the protection field
The SLG must be installed so that personnel are always located within 
the detection zone of the safety device when operating the hazardous 
machine parts to be secure

Correct installation

Hazardous machine parts can only be reached 

after passing through the protection field

The presence of staff members between the 

protection field and hazardous machine parts 

must be prevented/avoided (protection against 

stepping over)

Unauthorised installation

Hazardous machine parts can be reached  

without passing through the protection field

The presence of staff members between the 

protection field and hazardous machine parts  

is enabled

3.3  Alignment of the sensors
Procedure:

1  Transmitter and receiver must be fitted parallel to each other and at 

the same height

2 Choose the operating mode "Automatic" (see chapter Protective 
mode/automatic) and switch the operating voltage on
3  The 7-segment display in the receiver shows the current signal qual-

ity/fine setting (signalling, see chapter "set-up mode") for 30 seconds 
Rotate the transmitter and then the receiver towards each other until 
you have the best possible signal strength of 3 horizontal bars (7 
segment display) (note that 2 horizontal bars is sufficient) Fix this 
position using the screws to the mounting angleIf the set-up is not 
possible within 30 seconds, change to set-up mode (see chapter 
"set-up mode") The set-up mode leads to the best possible position-
ing of the sensors through the basic setting (position of the first and 
last beam) and the optimisation of with the fine setting (total signal) 
 

Status indication of the LED

  

OSSD ON (green) is active, signal strength (orange) is not active

Summary of Contents for SLG440

Page 1: ...About this document 1 1 Function 1 1 2 Target group authorised qualiied personnel 1 1 3 Explanation of the symbols used 1 1 4 Appropriate use 2 1 5 General safety instructions 2 1 6 Warning about mis...

Page 2: ...liability for damages and malfunctions resulting from defective mounting or failure to comply with this operating instructions manual The manufacturer shall accept no liability for damages result ing...

Page 3: ...restart interlock restart interlock 2 Input voltage HIGH active 11 30 V Input voltage LOW inactive 0 2 0 V Input current HIGH 3 10 mA Input current LOW 0 3 mA Functions automatic mode restart interloc...

Page 4: ...tputs OSSD s ON state after switch on of the operating volt age or an interruption of the protection field The system switches the outputs only to ON state when an external command device restart butt...

Page 5: ...is required The contactor control is not activated upon delivery The function is activated in parameter setting mode P 4 Connection EDM Wiring of the receiver Kn1 Kn2 auxiliary contact of the last sw...

Page 6: ...signalled in the following way 7 segment display LED OSSD ON red active LED OSSD OFF green active Parameter setting 1 When S1 is briely pressed the display shows repeatedly Parameter P 1 not active f...

Page 7: ...lication machine The safety inspections must be conducted regularly The SLG must not be exposed to inflammable or explosive gasses The connecting cables must be connected in accordance with the instal...

Page 8: ...eceive signal OK Beam b no receive signal Beam a and beam b receive signals OK Indication basic setting The signal strength is displayed per beam with two segments for the first a and the last b beam...

Page 9: ...tion from which the hazardous area is accessed To calculate the minimum distances of the safety guards with regards to the hazardous point the EN ISO 13855 and EN ISO 13857 must be observed If an over...

Page 10: ...0900 04 XX 300 1024 1043 258 5 217 5 L1 Mounting distance mm between floor and slotted hole centre short end cap L2 Mounting distance mm between floor and slotted hole centre diagnostic window Overal...

Page 11: ...reen outputs H signal 24V Red outputs L signal 0V Yellow setting mode restart interlock manual reset 24 5 12 5 15 0 1 The integrated status indication does not change the mounting dimen sion B or the...

Page 12: ...N 0 VDC BU Earth connection Restart interlock manual reset bridge 1 By bridging restart 2 pin 5 and DOUT pin 6 the restart interlock manual reset is activated Connect S1 to Pin1 Protective mode Automa...

Page 13: ...power supply see techni cal specifications which meets the CE Directives Low Voltage Directives A power downtime of 20 ms must be bridged 2 Presence of a voltage supply with correct polarity at the S...

Page 14: ...ring the first putting into operation 5 The cables the connectors the caps and the mounting angles are in perfect condition 5 5 Cleaning If the optics cover of the sensors is extremely soiled the OSSD...

Page 15: ...blanking area s of fixed or floating objects with the selected parameter setting fault elimination repeat configuration in the parameter setting possibly adjust P 1 P 2 P 3 Configuration error in para...

Page 16: ...13144608 Person authorized for the compilation of the technical documentation Oliver Wacker M ddinghofe 30 42279 Wuppertal K A Schmersal GmbH Co KG M ddinghofe 30 D 42279 Wuppertal Postfach 24 02 63...

Reviews: