SRB 201ZH

Operating instructions
Safety-monitoring module

EN

8.3  Actuator configuration

Single-channel control with feedback circuit (Fig. 5)

•  Suitable for increase in capacity or number of contacts by means of 

contactors or relays with positive-guided contacts

•  

S

 = feedback circuit:  

If the feedback circuit is not required, establish a bridge

Dual-channel control with feedback circuit (Fig. 6)

•  Suitable for increase in capacity or number of contacts by means of 

contactors or relays with positive-guided contacts

•  

S

 = feedback circuit:  

If the feedback circuit is not required, establish a bridge

X1

X2

23

13

24

14

K

C

K

A

S

L1

N

K

A

K

C

X1

X2

23

13

24

14

K

B

K

C

K

D

K

A

K

B

L1

N

K

A

K

D

S

K

C

Fig. 5

Fig. 6

Differential control with feedback circuit (see Fig. 7)

•  Suitable for increase in capacity or number of contacts by means of 

contactors or relays with positive-guided contacts

•  

S

 = feedback circuit:  

If the feedback circuit is not required, establish a bridge

X1

X2

23

13

24

14

K

A

L1

N

K

A

S

a)

Fig 7 a) Enabling signal controller

8.4  Flow diagram

1

1

1

1

0

0

0

0

1

0

1

0

1

0

1

0

a)

b)

d)

c)

B)

A)

C)

D)

E)

F)

t

S

4)

3)

1)

2)

Fig. 8

Legend

1) uninterrupted workcycle;
2) Fault in feedback circuit;
3) Synchronous actuation fault t > 05 s
4) Fault button A, B before U

B

in ;

A) Operating voltage UB;
B)  Two-hand button A: the representation is related to the potentials  

at the terminals of the safety-monitoring module; 
a) NC contact S11; b) NO contact S12;

C)  Two-hand button B: the representation is related to the potentials  

at the terminals of the safety-monitoring module; 
c) NC contact S21; d) NO contact S22;

D) Simultaneity monitoring ts (synchronous actuation);
E) Feedback circuit X1-X2;
F) Output contacts 13-14, 23-24 potential-free