Operating instructions
Safety-monitoring module

SRB 201ZH

EN

1.6  Warning about misuse

In case of inadequate or improper use or manipulations of 
the safety-monitoring module, personal hazards or damage 
to machinery or plant components cannot be excluded The 
relevant requirements of the standards EN 1088 and  
EN ISO 13850 must be observed

1.7  Exclusion of liability

We shall accept no liability for damages and malfunctions resulting from 
defective mounting or failure to comply with this operating instructions 
manual The manufacturer shall accept no liability for damages resul-
ting from the use of unauthorised spare parts or accessories

For safety reasons, invasive work on the device as well as arbitrary re-
pairs, conversions and modifications to the device are strictly forbidden; 
the manufacturer shall accept no liability for damages resulting from 
such invasive work, arbitrary repairs, conversions and/or modifications 
to the device

The safety-monitoring module must only be used when the enclosure is 
closed, ie with the front cover fitted

2.  Product description

2.1  Ordering code

This operating instructions manual applies to the following types:

SRB 201ZH

Only if the information described in this operating instruc-
tions manual are realised correctly, the safety function and 
therefore the compliance with the Machinery Directive is 
maintained

2.2  Special versions

For special versions, which are not listed in the order code below 21, 
these specifications apply accordingly, provided that they correspond to 
the standard version

2.3  Destination and use

The safety-monitoring modules for integration in safety circuits are desi-
gned for fitting in control cabinets They are used for the safe evaluation 
of the signals of two actuating elements A + B and correspond to a type 
III/C two-hand control to DIN EN 574

The safety function is defined as the opening of the enabling circuits 13-
14 and 23-24 when one or both actuating elements A + B are released 
The safety-relevant current paths with the output contacts 13-14 and 
23-24 meet the following requirements under observation of a PFH 
value assessment (also refer to chapter 25 "Safety classification"):  
– Control category 4 – PL e to DIN EN ISO 13849-1  
– corresponds to SIL 3 to DIN EN 61508-2  
–  SILCL 3 to DIN EN 62061

To determine the Performance Level (PL) of the entire safety function 
(eg sensor, logic, actuator) to DIN EN ISO 13849-1, an analysis of all 
relevant components is required

2.4  Technical data
General data

 

Standards:

 

IEC/EN 60204-1, EN 60947-5-1;  

EN ISO 13849-1, IEC 61508

Climate resistance:

  

EN 60068-2-78

Mounting:  

Snaps onto standard DIN rail to EN 60715

Terminal designations:

  

EN 60947-1

Material of the housings:

 

Plastic, glass-fibre reinforced  

thermoplastic, ventilated

Material of the contacts:

 

AgSnO, self-cleaning, positive drive

Weight:

  

200 g

Start conditions: 

Automatic

Feedback circuit (Y/N):

 yes

Pull-in delay for automatic start:

 

typ 50 ms 

Response time:

 

typ 30 ms, max 37 ms

Bridging in case of voltage drops: 

 

typ 30 ms

Simultaneity monitoring:

 

≤ 0.5 s

Mechanical data

 

Connection type:

 

Screw connection

Cable section:

 

Min 0,25 mm² / max 2,5 mm²

Connecting cable:

  

rigid or flexible

Tightening torque for the terminals:

 

06 Nm

With removable terminals (Y/N):

 yes

Mechanical life: 

10 million operations

Electrical life:  

Derating curve available on request

Resistance to shock:

 

30 g / 11 ms

Resistance to vibrations to EN 60068-2-6:

 

10 … 55 Hz,  

amplitude 035 mm

Ambient conditions

 

Ambient temperature: 

−25 °C … +60 °C

Storage and transport temperature:

 

−40 °C … +85 °C

Protection class: 

Enclosure: IP40  

Terminals: IP20  

Clearance: IP54

Air clearances and creepage distances to IEC/EN 60664-1:

 

4 kV/2  

(basic insulation)

EMC rating:  

to EMC Directive

Electrical data

 

Contact resistance in new state:

 

max. 100 mΩ

Power consumption: 

max 12 W

Rated operating voltage U

e

:

 

24 VDC –10%/+10%,  

residual ripple max 10%

Fuse rating for the operating voltage:

 

Internal electronic trip: 

F1, F2: tripping current > 02 A 

F3: tripping current > 06 A

Monitored inputs

 

Cross-wire detection (Y/N): 

Yes

Wire breakage detection (Y/N): 

Yes

Earth leakage detection (Y/N): 

Yes

Number of NO contacts:

 2

Number of NC contacts:

 2

Cable length: 

1,500 m mit 15 mm² 
2,500 m mit 25 mm²

Conduction resistance:

 

max. 40 Ω

Outputs

 

Number of safety contacts:

 

2 (13-14; 23-24)

Number of auxiliary contacts:

 

1 (31-32)

Number of signalling outputs: 

0

Switching capacity of the safety contacts:

 

max 250 V, 6 A ohmic  

(inductive in case of  

appropriate protective wiring);  

min 10 V / 10 mA

Switching capacity of the auxiliary contacts:

 

24 VDC / 2 A

Protection of the safety contacts

external (I

k

 = 1000 A)  

to EN 60947-5-1  

Safety fuse 8 A quick blow, 63 A slow blow

Fuse rating for the auxiliary contacts:

 

25 A quick blow,  

2 A slow blow

Utilisation category to EN 60947-5-1:

 

AC-15: 230 V / 6 A  

DC-13: 24 V / 6 A

Dimensions H x W x D:

 

100 x 225 x 121 mm

The data specified in this manual are applicable when the component is 
operated with rated operating voltage U

e

 ±0%