SRB 201ZH

Operating instructions
Safety-monitoring module

EN

2.5  Safety classification

Standards:

 

EN ISO 13849-1, IEC 61508,  

EN 60947-5-1, DIN EN 574, EN 60204-1

PL:

 

up to e

Control category:

 

up to 4

DC: 

99% (high)

CCF: 

> 65 points

PFH value:

 

≤ 2,00 × 10

-8

/

h

SIL:

 

up to 3

Service life: 

20 years

The PFH value of 2.00 × 10

-8

/h applies to the combinations of contact 

load (current through enabling contacts) and number of switching cyc-
les (nop/y) mentioned in the table below At 365 operating days per year 
and a 24-hours operation, this results in the below-mentioned switching 
cycle times (t

cycle

) for the relay contacts

Diverging applications upon request

Contact load

n

op/y

t

cycle

20 %

525,600

10 min

40 %

210,240

25 min

60 %

75,087

70 min

80 %

30,918

170 min

100 %

12,223 

430 min

3.  Mounting

3.1  General mounting instructions

Mounting: snaps onto standard DIN rails to EN 60715

Snap the bottom of the enclosure slightly tilted forwards in the DIN rail 
and push up until it latches in position

3.2  Dimensions

All measurements in mm
Device dimensions (H/W/D): 100 x 225 x 121 mm

with plugged-in terminals: 120 × 22.5 × 121 mm

4.  Electrical connection

4.1  General information for electrical connection

The electrical connection may only be carried out by  
authorised personnel in a de-energised condition

As far as the electrical safety is concerned, the protection 
against unintentional contact of the connected and therefore 
electrically interconnected apparatus and the insulation of the 
feed cables must be designed for the highest voltage, which 
can occur in the device

Wiring examples: see appendix

5.  Operating principle and settings

5.1  LED functions

 K1: Status channel 1
 K2: Status channel 2

5.2  Description of the terminals

Voltages:

A1

A11

A2

A21

+24 VDC

+ 24 V

0 VDC

0 V

Inputs:

S11

S12

S21

S22

Input channel 1 (+)

Input channel 1 (−)
Input channel 2 (−)

Input channel 2 (+)

Outputs:

13 - 14

23 - 24

31 - 32

First safety enabling circuit

Second safety enabling circuit

Auxiliary NC contact as signalling contact

Start:

X1 - X2

Feedback circuit

K1

K2

SRB 
201ZH

A1 23 13

X1 S12 S11

X2 S22 S21

A2 24 14

31

A1.1

A2.1

32

Fig. 1

5.3  Notes

Signalling outputs must not be used in safety circuits

The NC contact of the buttons A + B must be opened, before 
the NO contact closes No overlapping contacts to avoid 
triggering of the fuses F1 and F2

The pushbuttons A + B must be actuated within a timeframe 

of ≤ 0.5 sec (simultaneous operation monitoring), otherwise 

no start enabling signal is given!