background image

3

SRB 207AN-230V

Operating instructions

Safety-monitoring module

EN

3.  Mounting

3.1  General mounting instructions

Mounting: snaps onto standard DIN rails to EN 60715.

3.2  Dimensions

Device dimensions (H/W/D): 100 x 45 x 121 mm

4.  Electrical connection

4.1  General information for electrical connection

As far as the electrical safety is concerned, the protection 

against unintentional contact of the connected and therefore 

electrically interconnected apparatus and the insulation of the 

feed cables must be designed for the highest voltage, which 

can occur in the device.

The electrical connection may only be carried out by 

authorised personnel in a de-energised condition.

Wiring examples: see appendix

5.  Operating principle and settings

5.1  Operating principle after the operating voltage is switched on

With the guard door closed or the emergency stop command devices 

unlocked, the enabling paths are closed as soon as the start button is 

pushed. During the start command, the falling edge is detected, when 

the contacts of the downstream relays acting on the feedback circuit 

are closed.

If the safety guard is opened or the emergency-stop button is actuated, 

the enabling paths of the safety-monitoring module will open.  

The machine is stopped and the LED K1 and K2 will go out.  

The corresponding signal output signals which guard was opened.

Inputs   S11/S12-S22/S73/S74; 

S31/S32-S42/S83/S84; 

S51/S52-S62/S93/S94

Safety switches or emergency stop command devices with one NC 

and one NO contact must be connected to the inputs. If not all inputs 

are wired, a bridge must be established between Sx1 and Sx2 of the 

non-used input.

Start button/Feedback loop: X1/X2

Connect start button/feedback circuit to the inputs X1 and X2 according 

to the wiring diagram

Automatic start X1-X3

The automatic start is programmed by connecting the feedback circuit 

to the terminals X1-X3. If no start button and no feedback circuit is 

used, a bridge must be established between X1 and X3.

Outputs

Enabling paths 13-14, 23-24: NO contacts for safety function

Signalling output Y1-Y6

0 V  

safety guard open / no enabling signal

24 V  

safety guard closed / enabling signal

Auxiliary contact A1.1-32

Conditions of the enabling paths

Signalling outputs must not be used in safety circuits.

Due to the operating principle of the electronic fuse, the  

customer must check that no hazard is caused by an  

unexpected restart in circuits without reset button  

(automatic reset).

6.  Set-up and maintenance

6.1  Functional testing

The safety function of the safety-monitoring module must be tested. 

The following conditions must be previously checked and met:

1. Fitting of the safety monitoring module

2. Fitting and integrity of the power cable

6.2  Maintenance

In the case of correct installation and adequate use, the safety-

monitoring module features maintenance-free functionality.

A regular visual inspection and functional test, including the following 

steps, is recommended:

• Check the correct fixing of the safety-monitoring module

• Check the cable for damage.

If a manual functional check is necessary to detect a possible 

accumulation of faults, then this must take place during the 

intervals noted as follows:

•  at least every month for PL e with category 3 or  

category 4 (according to ISO 13849-1) or SIL 3 with HFT 

(hardware fault tolerance) = 1 (according to IEC 62061);

•  at least every 12 months for PL d with category 3  

(according to ISO 13489-1) or SIL 2 with HFT  

(hardware fault tolerance) = 1 (according to IEC 62061).

Damaged or defective components must be replaced.

7.  Disassembly and disposal

7.1  Disassembly

The safety-monitoring module must be disassembled in a de-energised 

condition only.

7.2  Disposal

The safety-monitoring module must be disposed of in an appropriate 

manner in accordance with the national prescriptions and legislations.

8.  Appendix

8.1  Wiring example

The application examples shown are suggestions. They however do not 

release the user from carefully checking whether the switchgear and its 

set-up are suitable for the individual application

The wiring diagram is shown with guard doors closed and in a  

de-energised condition. Inductive loads (e.g. contactors, relays, etc.) 

are to be provided with suitable interference suppression circuitry.  

Do not connect additional loads to terminal S..

Reviews: