2

Operating instructions
Safety-monitoring module

SRB 211AN V.2 / CC V.2 / PC V.2

EN

1.6  Warning about misuse

In case of inadequate or improper use or manipulations of 
the safety-monitoring module, personal hazards or damage 
to machinery or plant components cannot be excluded. The 
relevant requirements of the standards EN 1088 and  
EN ISO 13850 must be observed.

1.7  Exclusion of liability

We shall accept no liability for damages and malfunctions resulting from 
defective mounting or failure to comply with this operating instructions 
manual. The manufacturer shall accept no liability for damages resul-
ting from the use of unauthorised spare parts or accessories.

For safety reasons, invasive work on the device as well as arbitrary re-
pairs, conversions and modifications to the device are strictly forbidden; 
the manufacturer shall accept no liability for damages resulting from 
such invasive work, arbitrary repairs, conversions and/or modifications 
to the device.

The safety-monitoring module must only be used when the enclosure is 
closed, i.e. with the front cover fitted.

2.  Product description

2.1  Ordering code

This operating instructions manual applies to the following types:

SRB 211AN

 

V.2

No.

Option

Description

Plug-in screw terminals 0.25…2.5 mm²

/CC

Plug-in cage clamps 0.25 … 1.5 mm²

/PC

Screw terminals 0.25…2.5 mm²

Only if the information described in this operating instructions 
manual are realised correctly, the safety function and there-
fore the compliance with the Machinery Directive is maintained.

2.2  Special versions

For special versions, which are not listed in the order code below 2.1, 
these specifications apply accordingly, provided that they correspond to 
the standard version.

2.3  Destination and use

The safety-monitoring modules for integration in safety circuits are desi-
gned for fitting in control cabinets. They are used for the safe evaluation 
of the signals of positive break position switches for safety functions 
or magnetic safety sensors on sliding, hinged and removable safety 
guards as well as emergency stop control devices.

The safety function is defined as the opening of the enabling circuits 
13-14 and 23-24 and the delayed opening of the enabling circuits 37-38 
when the input S21-S22 is opened and/or when the input S13-S14 is 
closed. The safety-relevant current paths with the output contacts 13-14 
and 23-24 meet the following requirements under observation of a  
B

10d

 value assessment (also refer to chapter 2.5 "Safety classification"):  

– Control category 4 – PL e to DIN EN ISO 13849-1  
– Corresponds to SIL 3 to DIN EN 61508-2  
– SILCL 3 to DIN EN 62061

The safety-relevant current paths with the outputs contacts 37-38 meet 
the following requirements under observation of a B

10d

 value assess-

ment (also refer to chapter 2.5 "Safety classification"):  
– Control category 3 - PL d to DIN EN ISO 13849-1 
– SIL 2 to DIN EN 61508-2 
– SILCL 2 to DIN EN 62061

To determine the Performance Level (PL) of the entire safety function 
(e.g. sensor, logic, actuator) to DIN EN ISO 13849-1, an analysis of all 
relevant components is required.

2.4  Technical data
General data: 

Standards:

 

IEC/EN 60204-1, EN 60947-5-1,  

EN ISO 13849-1, IEC/EN 61508

Climate resistance:

 

EN 60068-2-78

Mounting:

 

Snaps onto standard DIN rail to EN 60715

Terminal designations:

 

EN 60947-1

Material of the housings:

 

Plastic, glass-fibre reinforced  

thermoplastic, ventilated

Material of the contacts:

 

AgSnO, AgNi,  

self-cleaning, positive drive

Weight:

 

230 g

Start conditions:

 

Automatic or start button (monitored)

Feedback circuit available:

 yes

Pull-in delay for automatic start: 

 

typ. 120 ms, max. 130 ms

Pull-in delay with reset button:

 

typ. 10 ms, max. 15 ms

Drop-out delay in case of emergency stop:

 

typ. 15 ms, max. 20 ms

Drop-out delay on "supply failure":

 

≤ 55 ms

Bridging in case of voltage drops:

 

≤ 40 ms

Mechanical data: 

Connection type:

 

refer to 2.1 Ordering code

Cable section:

 

refer to 2.1 Ordering code

Connecting cable:

 

rigid or flexible

Tightening torque for the terminals: 

 

0.6 Nm

With removable terminals:

 

refer to 2.1 Ordering code

Mechanical life:

 

10 million operations

Resistance to shock:

 

10 g / 11 ms

Resistance to vibrations to EN 60068-2-6:

 

10 … 55 Hz,  

amplitude 0.35 mm

Ambient temperature:

 

–25 °C … +60 °C

Storage and transport temperature:

 

–40 °C … +85 °C

Protection class:

 

Enclosure: IP40  

Terminals: IP20  

Clearance: IP54

Air clearances and creepage distances  

 

to IEC/EN 60664-1:

 

4 kV/2 (basic insulation)

EMC rating: 

 

to EMC Directive

Electrical data: 

Contact resistance in new state:

 

max. 100 mΩ

Power consumption:

 

2.4 W / 5.9 VA,  

plus signalling output

Rated operating voltage U

e

:

 

24 VDC: –15% / +20%,  

residual ripple max. 10%  

24 VAC: –15% / +10%

Frequency range:

 

50 / 60 Hz

Fuse rating for the operating voltage:

 

Internal electronic trip,  

tripping current F1: > 750 mA; 

tripping current F2: > 75 mA; 

Reset after disconnection of supply voltage; 

tripping current F3: > 140 mA

Current and voltage at the control circuits: 

 

- S13, S14, S21, S22:

 

24 VDC, 10 mA 

- X1, X2:

 

24 VDC, start impulse 25 mA / 25 ms 

- X1, X3:

 

24 VDC, start impulse 950 mA / 10 ms

Monitored inputs: 

Cross-wire detection:

 yes

Wire breakage detection:

 yes

Earth connection detection:

 yes

Number of NO contacts:

 1

Number of NC contacts:

 1

Cable length:

 

1,500 m mit 1.5 mm² 
2,500 m mit 2.5 mm²

Conduction resistance:

 

max. 40 Ω

Summary of Contents for SRB 211AN V.2

Page 1: ...acturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this o...

Page 2: ...ontrol category 4 PL e to DIN EN ISO 13849 1 Corresponds to SIL 3 to DIN EN 61508 2 SILCL 3 to DIN EN 62061 The safety relevant current paths with the outputs contacts 37 38 meet the following require...

Page 3: ...75 087 7 0 min 80 30 918 17 0 min 100 12 223 43 0 min 2 6 Derating curve 21 A 18 A 15 A 12 A 9 A 6 A 3 A 0 A 35 C 40 C 45 C 50 C 55 C 60 C 65 C Fig 1 vertical residual current horizontal ambient tempe...

Page 4: ...hes can be set when the operating voltage is on however in order for the setting to be saved in the SRB 211ST the voltage supply must be interrupted for approx 3 seconds The set drop out delay must be...

Page 5: ...sposal The safety monitoring module must be disposed of in an appropriate manner in accordance with the national prescriptions and legislations 8 Appendix 8 1 Wiring examples Dual channel control show...

Page 6: ...hing current min 10 mA For example the following safety sensors meet the requirements BNS 33 11z BNS 33 11z 2063 BNS 33 11zG 2237 BNS 250 11z BNS 250 11zG BNS 120 11z BNS 180 11z BNS 303 11z BNS 303 1...

Page 7: ...Person authorized for the compilation of the technical documentation Oliver Wacker M ddinghofe 30 42279 Wuppertal Notiied body which approved the full quality assurance system referred to in Appendix...

Page 8: ...KG Industrielle Sicherheitsschaltsysteme M ddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Telefon 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E mail info schmersal com Internet...

Reviews: