3

SRB 301/CL1

Operating instructions

Safety-monitoring module

EN

2.5  Safety classification

Standards:

 

EN ISO 13849-1, IEC 61508, EN 60947-5-1

PL:

 

Stop 0: up to e

Category:

 

Stop 0: up to 4

DC:

 

Stop 0: 99% (high)

CCF:

 

> 65 points

SIL:

 

Stop 0: up to 3

Service life: 

20 years

B

10D

 value (for one channel):

 

Low voltages range 20%: 20,000,000 

40%: 7,500,000 

60%: 2,500,000 

80%: 1,000,000 

Maximum load 100%: 400,000

MTTF

B

d x

x

h

s/h

3600

D

10D

op

op

op

n

0,1 x n

op

t

cycle

For an average annual demand rate of n

op

 = 126,720 cycles per year, 

Performance Level PL e can be obtained at maximum load.

n

op

 

= average number of activations per year

d

op

 

= average number of operating days per year

h

op

 

= average number of operating hours per day

t

cycle

 

=  average demand rate of the safety function in s  

(e.g. 4 × per hour = 1 × per 15 min. = 900 s)

(Specifications can vary depending on the application-specific 

parameters h

op

, d

op

 and t

cycle

 as well as the load.)

3.  Mounting

3.1  General mounting instructions

Mounting: snaps onto standard DIN rails to EN 60715.

Snap the bottom of the enclosure slightly tilted forwards in the DIN rail 

and push up until it latches in position.

3.2  Dimensions

All measurements in mm.

Device dimensions (H/W/D): 100 x 22.5 x 121 mm

4.  Rear side Electrical connection

4.1  General information for electrical connection

The electrical connection may only be carried out by 

authorised personnel in a de-energised condition.

Wiring examples: see appendix

5.  Operating principle and settings

5.1  LED functions

• K1: Status channel 1

• K2: Status channel 2

•   U

B

: Status operating voltage (LED is on, when the operating voltage 

on the terminals A1-A2 is ON)

•   U

i

: Status internal operating voltage (LED is on, when the operating 

voltage on the terminals C-D is ON and the fuse has not been 

triggered)

5.2  Description of the terminals

Voltages: C

D

+24 VDC/24 VAC
0 VDC/24 VAC

Inputs:

C1-S1
C1-D1
D1-S2

Input channel 1 (+)
Input channel 2 (+)
Input channel 2 (–) (with cross-wire short detection)

Outputs: 13-14

23-24
33-34

First safety enabling circuit
Second safety enabling circuit
Third safety enabling circuit

Start:

X1-X2
41-42

Feedback circuit and external reset
Auxiliary NC contact

U

B

U

i

K1

K2

SRB 

301/

CL1

C C1 23

13 S1 24

33

41

14 D1 D

X2 S2 X1

34

42

*

Fig. 1
* = with printed customer-specific logo

5.3  Notes

Due to the operating principle of the electronic fuse, the customer 

must check that no hazard is caused by an unexpected restart in 

circuits without reset button (automatic reset).

6.  Set-up and maintenance

6.1  Functional testing

The safety function of the safety-monitoring module must be tested. 

The following conditions must be previously checked and met:

1. Correct fixing

2. Check the integrity of the cable entry and connections

3.  Check the safety-monitoring module's enclosure for damage

4.  Check the electrical function of the connected sensors and their 

influence on the safety-monitoring module and the downstream 

actuators

6.2  Maintenance

A regular visual inspection and functional test, including the following 

steps, is recommended:

1. Check the correct fixing of the safety-monitoring module

2. Check the cable for damages

3. Check electrical function

Damaged or defective components must be replaced.