2

Operating instructions

Safety-monitoring module

SRB 301/CL1

EN

There are no residual risks, provided that the safety instructions as well 

as the instructions regarding mounting, commissioning, operation and 

maintenance are observed.

1.6  Warning about misuse

In case of inadequate or improper use or manipulations of the 

safety-monitoring module, personal hazards or damage to 

machinery or plant components cannot be excluded. The relevant 

requirements of the standard EN 1088 must be observed.

1.7  Exclusion of liability

We shall accept no liability for damages and malfunctions resulting from 

defective mounting or failure to comply with this operating instructions 

manual. The manufacturer shall accept no liability for damages 

resulting from the use of unauthorised spare parts or accessories.

For safety reasons, invasive work on the device as well as arbitrary 

repairs, conversions and modifications to the device are strictly 

forbidden; the manufacturer shall accept no liability for damages 

resulting from such invasive work, arbitrary repairs, conversions and/or 

modifications to the device.

The safety-monitoring module must only be used when the enclosure  

is closed, i.e. with the front cover fitted.

2.  Product description

2.1  Ordering code

This operating instructions manual applies to the following types:

SRB 301/CL1

Only if the information described in this operating instructions 

manual are realised correctly, the safety function and therefore 

the compliance with the Machinery Directive is maintained.

2.2  Special versions

For special versions, which are not listed in the order code below 2.1, 

these specifications apply accordingly, provided that they correspond to 

the standard version.

2.3  Purpose

The safety-monitoring modules for integration in safety circuits are 

designed for fitting in control cabinets. They are used for the safe 

evaluation of the signals of positive break position switches for safety 

functions on sliding, hinged and removable safety guards as well 

as emergency stop control devices. They have a defined switch-off 

behaviour in case of a momentary supply failure.

The safety function is defined as the opening of the enabling circuits  

13-14, 23-24 and 33-34 when the inputs C1-S1 and/or D1-S2 are 

opened. The safety-relevant current paths with output contacts 13-14, 

23-24 and 33-34 meet the following requirements under observation of 

a B

10D

 value assessment (also refer to “Requirements of  

DIN EN ISO 13849-1“):

– Control category 4 – PL e to DIN EN ISO 13849-1

– corresponds to SIL 3 to DIN EN 61508-2

–  corresponds to SILCL 3 to DIN EN 62061 

(corresponds to control category 4 to DIN EN 954-1)

To determine the Performance Level (PL) of the entire safety function 

(e.g. sensor, logic, actuator) to DIN EN ISO 13849-1, an analysis of all 

relevant components is required.

2.4  Technical data

General data 

Standards:

 

IEC/EN 60204-1, EN 60947-5-1,  

EN ISO 13849-1; IEC 61508

Climate resistance:

  

EN 60068-2-78

Mounting:  

Snaps onto standard DIN rail to EN 60715

Terminal designations:

  

EN 60947-1

Material of the housings:

 

Plastic, glass-fibre reinforced 

thermoplastic, ventilated

Material of the contacts:

 

AgSnO, self-cleaning, positive drive

Weight:

  

250 g

Start conditions:

 

Automatic or start button

Feedback circuit (Y/N):

 yes

Pull-in delay for automatic start:

 

typ. 110 ms

Pull-in delay with reset button:

 

typ. 20 ms

Drop-out delay in case of emergency stop:

 

typ. 30 ms

Drop-out delay on "supply failure":

 

typ. 30 ms

Bridging in case of voltage drops: 

 

typ. 20 ms

Mechanical data 

Connection type:

 

Screw connection

Cable section:

 

min. 0,25 mm² / max. 2,5 mm²

Connecting cable:

  

rigid or flexible

Tightening torque for the terminals: 

 

0.6 Nm

With removable terminals (Y/N):

 Nein

Mechanical life: 

10 million operations

Electrical life:  

Derating curve available on request

Resistance to shock:

 

10 g / 11 ms

Resistance to vibrations to EN 60068-2-6:

 

10 ... 55 Hz,  

amplitude 0.35 mm

Ambient conditions 

Ambient temperature:

 

– 25 °C … +45 °C

Storage and transport temperature:

 

–40 °C … +85 °C

Protection class: 

Enclosure: IP40  

Terminals: IP20  

Clearance: IP54

Air clearances and creepage distances  

to IEC/EN 60664-1:

 

4 kV/2 (basic insulation)

EMC rating:  

to EMC Directive

Electrical data 

Contact resistance in new state: 

 

max. 100 mΩ

Power consumption: 

max. 2 W

Rated operating voltage U

e

:

 

24 VDC –15% / +20%,  

 

residual ripple max. 10%,  

min. 10 V / 10 mA

Fuse rating for the operating voltage:

 

electronic fuse,  

 

Tripping current > 0.4 A;  

Reset after approx. 1 sec.

Monitored inputs 

Cross-wire detection (Y/N):  

Yes

Wire breakage detection (Y/N):  

Yes

Earth leakage detection (Y/N):  

Yes

Number of NO contacts:

 0

Number of NC contacts:

 2

Cable length:

 

–1,500 m = 1.5 mm² 

–2,500 m = 2.5 mm² 

2-channel with cross-wire short detection

Conduction resistance:

 

max. 40 Ω

Outputs 

Number of safety contacts:

 3

Number of auxiliary contacts: 

1

Number of signalling outputs:  

0

Switching capacity of the safety contacts:

 

13-14; 23-24; 33-34: 

max. 250 V, 6 A ohmic (inductive in case of 

appropriate protective wiring)

Switching capacity of the auxiliary contacts:

 

41-42: 24 VDC / 2 A

Fuse rating of the safety contacts:

 

6.3 A slow blow 

Recommended fuse for the auxiliary contacts:  

2 A slow blow

Utilisation category to IEC/EN 60947-5-1:

 

AC-15 / DC-13:  

EN 60947-5-1

Dimensions H x W x D:

 

100 mm x 22,5 mm x 121 mm

The data specified in this manual are applicable when the component is 

operated with rated operating voltage U

e

 ±0%.