1.  About this document

1.1  Function

This operating instructions manual provides all the information you 

need for the mounting, set-up and commissioning to ensure the safe 

operation and disassembly of the safety-monitoring module. The 

operating instructions must be available in a legible condition and a 

complete version in the vicinity of the device.

1.2  Target group: authorised qualified personnel

All operations described in this operating instructions manual must 

be carried out by trained specialist personnel, authorised by the plant 

operator only.

Please make sure that you have read and understood these operating 

instructions and that you know all applicable legislations regarding 

occupational safety and accident prevention prior to installation and 

putting the component into operation.

The machine builder must carefully select the harmonised standards 

to be complied with as well as other technical specifications for the 

selection, mounting and integration of the components.

1.3  Explanation of the symbols used

Information, hint, note:

This symbol is used for identifying useful additional information.

Caution:

 Failure to comply with this warning notice could 

lead to failures or malfunctions.

Warning:

 Failure to comply with this warning notice could 

lead to physical injury and/or damage to the machine.

1.4  Appropriate use

The products described in these operating instructions are developed to 

execute safety-related functions as part of an entire plant or machine. It 

is the responsibility of the manufacturer of a machine or plant to ensure 

the correct functionality of the entire machine or plant.

The safety-monitoring module must be exclusively used in accordance 

with the versions listed below or for the applications authorised by the 

manufacturer. Detailed information regarding the range of applications 

can be found in the chapter "Product description".

1.5  General safety instructions

The user must observe the safety instructions in this operating 

instructions manual, the country-specific installation standards as well 

as all prevailing safety regulations and accident prevention rules.

Further technical information can be found in the Schmersal 

catalogues or in the online catalogue on the Internet:  

www.schmersal.net.

The information contained in this operating instructions manual is 

provided without liability and is subject to technical modifications. There 

are no residual risks, provided that the safety instructions as well as 

the instructions regarding mounting, commissioning, operation and 

maintenance are observed.

Content

1  About this document

1.1  Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

1.2 

Target group: authorised qualified personnel

. . . . . . . . . . . . . . . . . .1

1.3  Explanation of the symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . .1

1.4  Appropriate use  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

1.5  General safety instructions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

1.6  Warning about misuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

1.7  Exclusion of liability  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

2  Product description

2.1  Ordering code  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

2.2  Special versions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

2.3  Destination and use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

2.4  Technical data  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

2.5 

Safety classification

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

3  Mounting

3.1  General mounting instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

3.2  Dimensions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

4  Electrical connection

4.1  General information for electrical connection. . . . . . . . . . . . . . . . . .3

5  Operating principle and settings

5.1  LED functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

5.2  Description of the terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

5.3  Notes  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

6  Set-up and maintenance

6.1  Functional testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

6.2  Maintenance  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

7  Disassembly and disposal

7.1  Disassembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

7.2  Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

8  Appendix

8.1  Wiring examples  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

8.2 

Start configuration

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

8.3 

Sensor configuration

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

8.4 

Actuator configuration

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

9  EU Declaration of conformity

x.000 / 07.2016 / v

.A.   -   101

190702-EN / K / 2016-07-04 / 

AE-Nr

. 6259

EN

Operating instructions. . . . . . . . . . . . .pages 1 to 8

Original

Summary of Contents for SRB 301MC-ST

Page 1: ...ule must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual the country specific installation standards as wel...

Page 2: ...t the following requirements under observation of a PFH value assessment also refer to chapter 2 5 Safety classification Control category 4 PL e to ISO 13849 1 1 SIL 3 to IEC 61508 2 SILCL 3 to IEC 62061 To determine the Performance Level PL to ISO 13849 1 1 of the entire safety function e g sensor logic actuator an assessment of all relevant components is required The entire concept of the contro...

Page 3: ... 223 43 0 min 3 Mounting 3 1 General mounting instructions Mounting snaps onto standard DIN rails to EN 60715 Snap the bottom of the enclosure slightly tilted forwards in the DIN rail and push up until it latches in position To avoid EMC disturbances the physical ambient and opera tional conditions at the place where the product is installed must meet the provisions laid down in the paragraph Elec...

Page 4: ...33 S12 14 24 34 S21 42 X2 A2 S22 41 X1 A1 S12 18 28 38 S22 45 X1 A1 nQS QS Fig 1 Fig 2 Fig 3 6 Set up and maintenance 6 1 Functional testing The safety function of the safety monitoring module must be tested The following conditions must be previously checked and met 1 Correct fixing 2 Check the integrity of the cable entry and connections 3 Check the safety monitoring module s enclosure for damag...

Page 5: ...ration Single channel emergency stop circuit with command devices to ISO 13850 and IEC 60947 5 5 Fig 7 Wire breakage and earth leakage in the control circuits are detected Category 1 PL c to ISO 13849 1 1 possible Dual channel emergency stop circuit with command devices to ISO 13850 and IEC 60947 5 5 Fig 8 Wire breakage and earth leakage in the control circuits are detected Cross wire shorts betwe...

Page 6: ...ety monitoring module is only admitted when the requirements of the standard IEC 60947 5 3 are observed As the technical data are regarded the following minimum requirements must be met switching capacity min 240 mW switching voltage min 24 VDC switching current min 10 mA For example the following safety sensors meet the requirements BNS33 02z 2187 BNS33 02zG 2187 BNS260 02z BNS260 02zG BNS260 02 ...

Page 7: ...2010 Notified body for the prototype test TÜV Rheinland Industrie Service GmbH Alboinstr 56 12103 Berlin ID n 0035 EC prototype test certificate 01 205 5035 01 16 Person authorized for the compilation of the technical documentation Oliver Wacker Möddinghofe 30 42279 Wuppertal Place and date of issue Wuppertal April 26 2016 Authorised signature Philip Schmersal Managing Director EU Declaration of c...

Page 8: ... A Schmersal GmbH Co KG Möddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal com ...

Reviews: