SRB 301MC

SRB 301MC-ST

Operating instructions

Safety-monitoring module

EN

Outputs:

 

Number of safety contacts:

 3

Number of auxiliary contacts:

 1

Number of signalling outputs:

 0

Max. switching capacity of the safety contacts:

 

13-14; 23-24; 33-34:  

max. 250 V, 8 A ohmic  

(inductive in case of suitable protective wiring);  

min. 10 V / 10 mA, residual current at  

ambient temperature up to:  

45 °C: 24 A ; 55 °C: 18 A; 60 °C: 12 A

Switching capacity of the auxiliary contacts:

 

41-42: 24 VDC / 2 A

Fuse rating of the safety contacts: 

 

external (I

k

 = 1000 A)  

to IEC 60947-5-1 

 

Safety fuse 10 A quick blow, 8 A slow blow

Fuse rating for the auxiliary contacts: 

 

external (I

k

 = 1000 A)  

to IEC 60947-5-1 

 

Safety fuse 2.5 A quick blow, 2 A slow blow

Utilisation category to IEC 60947-5-1:

 

AC-15 / DC-13: 

 

IEC 60947-5-1

Dimensions H x W x D:

 

SRB 301MC: 100 x 22.5 x 121 mm

 

SRB 301MC-ST: 120 x 22.5 x 121 mm

The data specified in this manual are applicable when the component is 

operated with rated operating voltage U

e

 ±0%.

2.5  Safety classification

Standards:

 

ISO 13849-1, IEC 61508, IEC 60947-5-1

PL:

 

up to e

Control category:

 

up to 4

DC: 

99% (high)

CCF: 

> 65 points

PFH value:

 

≤ 2.00 × 10

-8

/h

SIL:

 

up to 3

Service life:

 

20 years

The PFH value of 2.00 × 10

-8

/h applies to the combinations of contact 

load (current through enabling contacts) and number of switching 

cycles (n

op/y

) mentioned in the table below. At 365 operating days per 

year and a 24-hours operation, this results in the below-mentioned 

switching cycle times (t

cycle

) for the relay contacts.

Diverging applications upon request.

Contact load

n

op/y

t

cycle

20 %

525,600

1.0 min

40 %

210,240

2.5 min

60 %

75,087

7.0 min

80 %

30,918

17.0 min

100 %

12,223 

43.0 min

3.  Mounting

3.1  General mounting instructions

Mounting: snaps onto standard DIN rails to EN 60715.

Snap the bottom of the enclosure slightly tilted forwards in the DIN rail 

and push up until it latches in position.

To avoid EMC disturbances, the physical ambient and opera

-

tional conditions at the place where the product is installed, 

must meet the provisions laid down in the paragraph "Electro-

magnetic Compatibility (EMC)" of EN 60204-1.

3.2  Dimensions

All measurements in mm.

Device dimensions (H/W/D):

SRB 301MC:  

100 x 22.5 x 121 mm

SRB 301MC-ST:  

120 x 22.5 x 121 mm

4.  Electrical connection

4.1  General information for electrical connection

As far as the electrical safety is concerned, the protection 

against unintentional contact of the connected and therefore 

electrically interconnected apparatus and the insulation of the 

feed cables must be designed for the highest voltage, which 

can occur in the device.

The electrical connection may only be carried out by  

authorised personnel in a de-energised condition.

Wiring examples: see appendix

5.  Operating principle and settings

5.1  LED functions

•  K1: Status channel 1

•  K2: Status channel 2

•  U

B

: Status operating voltage (LED is on, when the operating voltage 

on the terminals A1-A2 is ON)

•  U

i

: Status internal operating voltage (LED is on, when the operating 

voltage on the terminals A1-A2 is ON and the fuse has not been 

triggered).

5.2  Description of the terminals

Voltages:

A1
A2

+24 VDC/24 VAC

 

0 VDC/0 VAC

Inputs:

S11 - S12
S21 - S22

S21 - S22

Input channel 1 (+)
Input channel 2 (+) (without cross-wire 

short detection)
Input channel 2 (–) (with cross-wire  
short detection)

Outputs:

13 - 14
23 - 24
33 - 34
41 - 42

First safety enabling circuit
Second safety enabling circuit
Third safety enabling circuit

Auxiliary NC contact as signalling contact

Start:

X1 - X2

Feedback circuit and external reset

Summary of Contents for SRB 301MC-ST

Page 1: ...ule must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual the country specific installation standards as wel...

Page 2: ...t the following requirements under observation of a PFH value assessment also refer to chapter 2 5 Safety classification Control category 4 PL e to ISO 13849 1 1 SIL 3 to IEC 61508 2 SILCL 3 to IEC 62061 To determine the Performance Level PL to ISO 13849 1 1 of the entire safety function e g sensor logic actuator an assessment of all relevant components is required The entire concept of the contro...

Page 3: ... 223 43 0 min 3 Mounting 3 1 General mounting instructions Mounting snaps onto standard DIN rails to EN 60715 Snap the bottom of the enclosure slightly tilted forwards in the DIN rail and push up until it latches in position To avoid EMC disturbances the physical ambient and opera tional conditions at the place where the product is installed must meet the provisions laid down in the paragraph Elec...

Page 4: ...33 S12 14 24 34 S21 42 X2 A2 S22 41 X1 A1 S12 18 28 38 S22 45 X1 A1 nQS QS Fig 1 Fig 2 Fig 3 6 Set up and maintenance 6 1 Functional testing The safety function of the safety monitoring module must be tested The following conditions must be previously checked and met 1 Correct fixing 2 Check the integrity of the cable entry and connections 3 Check the safety monitoring module s enclosure for damag...

Page 5: ...ration Single channel emergency stop circuit with command devices to ISO 13850 and IEC 60947 5 5 Fig 7 Wire breakage and earth leakage in the control circuits are detected Category 1 PL c to ISO 13849 1 1 possible Dual channel emergency stop circuit with command devices to ISO 13850 and IEC 60947 5 5 Fig 8 Wire breakage and earth leakage in the control circuits are detected Cross wire shorts betwe...

Page 6: ...ety monitoring module is only admitted when the requirements of the standard IEC 60947 5 3 are observed As the technical data are regarded the following minimum requirements must be met switching capacity min 240 mW switching voltage min 24 VDC switching current min 10 mA For example the following safety sensors meet the requirements BNS33 02z 2187 BNS33 02zG 2187 BNS260 02z BNS260 02zG BNS260 02 ...

Page 7: ...2010 Notified body for the prototype test TÜV Rheinland Industrie Service GmbH Alboinstr 56 12103 Berlin ID n 0035 EC prototype test certificate 01 205 5035 01 16 Person authorized for the compilation of the technical documentation Oliver Wacker Möddinghofe 30 42279 Wuppertal Place and date of issue Wuppertal April 26 2016 Authorised signature Philip Schmersal Managing Director EU Declaration of c...

Page 8: ... A Schmersal GmbH Co KG Möddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal com ...

Reviews: