1. About this document

1.1  Function

This operating instructions manual provides all the information you 

need for the mounting, set-up and commissioning to ensure the safe 

operation and disassembly of the safety-monitoring module. The 

operating instructions must be available in a legible condition and a 

complete version in the vicinity of the device.

1.2  Target group: authorised qualified personnel

All operations described in this operating instructions manual must 

be carried out by trained specialist personnel, authorised by the plant 

operator only.

Please make sure that you have read and understood these operating 

instructions and that you know all applicable legislations regarding 

occupational safety and accident prevention prior to installation and 

putting the component into operation.

The machine builder must carefully select the harmonised standards 

to be complied with as well as other technical specifications for the 

selection, mounting and integration of the components.

1.3  Explanation of the symbols used

Information, hint, note:

This symbol is used for identifying useful additional information.

Caution:

 Failure to comply with this warning notice could 

lead to failures or malfunctions.

Warning:

 Failure to comply with this warning notice could 

lead to physical injury and/or damage to the machine.

1.4  Appropriate use

The products described in these operating instructions are developed to 

execute safety-related functions as part of an entire plant or machine. It 

is the responsibility of the manufacturer of a machine or plant to ensure 

the correct functionality of the entire machine or plant.

The safety-monitoring module must be exclusively used in accordance 

with the versions listed below or for the applications authorised by the 

manufacturer. Detailed information regarding the range of applications 

can be found in the chapter "Product description".

To avoid EMC disturbances, the physical ambient and 

operational conditions at the place where the product is 

installed, must meet the provisions laid down in the paragraph 

"Electromagnetic Compatibility (EMC)" of DIN EN 60204-1.

1.5  General safety instructions

The user must observe the safety instructions in this operating 

instructions manual, the country-specific installation standards as well 

as all prevailing safety regulations and accident prevention rules.

Further technical information can be found in the Schmersal 

catalogues or in the online catalogue on the Internet:  

www.schmersal.net.

The information contained in this operating instructions manual is 

provided without liability and is subject to technical modifications.

Content

1  About this document

1.1  Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

1.2 

Target group: authorised qualified personnel

. . . . . . . . . . . . . . . . . .1

1.3  Explanation of the symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . .1

1.4  Appropriate use  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

1.5  General safety instructions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

1.6  Warning about misuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

1.7  Exclusion of liability  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

2  Product description

2.1  Ordering code  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

2.2  Special versions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

2.3  Destination and use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

2.4  Technical data  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

2.5 

Safety classification

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

3  Mounting

3.1  General mounting instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

3.2  Dimensions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

4  Rear side Electrical connection

4.1  General information for electrical connection. . . . . . . . . . . . . . . . . .3

5  Operating principle and settings

5.1  LED functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

5.2  Description of the terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

5.3  Notes  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

6  Set-up and maintenance

6.1  Functional testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

6.2  Maintenance  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

7  Disassembly and disposal

7.1  Disassembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

7.2  Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

8  Appendix

8.1  Wiring examples  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

8.2 

Start configuration

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

8.3 

Sensor configuration

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

8.4 

Actuator configuration

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

9  EU Declaration of conformity

x.000 / 

August 2017 / v

.A. - 101

193020-EN / D / 2017-08-17 / 

AE-Nr

. 7730

EN

Operating instructions. . . . . . . . . . . . .pages 1 to 8

Original

Summary of Contents for SRB 304ST

Page 1: ... with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description To avoid EMC disturbances the physical ambient and operational conditions at the place where the product is installed must meet the provisions laid down in the paragraph Electromagnetic Compatibility EMC of D...

Page 2: ... S12 and or S21 S22 and or S31 S32 are opened The safety relevant current paths with the output contacts 13 14 23 24 and 33 34 meet the following requirements under observation of a PFH value assessment also refer to chapter 2 5 Safety classification Control category 4 PL e to DIN EN ISO 13849 1 Corresponds to SIL 3 to DIN EN 61508 2 SILCL 3 to DIN EN 62061 To determine the Performance Level PL of...

Page 3: ... 918 17 0 min 100 12 223 43 0 min 3 Mounting 3 1 General mounting instructions Mounting snaps onto standard DIN rails to EN 60715 Snap the bottom of the enclosure slightly tilted forwards in the DIN rail and push up until it latches in position 3 2 Dimensions All measurements in mm Device dimensions H W D 100 x 45 x 121 mm with plugged in terminals 120 45 121 mm 4 Rear side Electrical connection 4...

Page 4: ...3 If the hybrid fuse is not activated Y3 is supplied with operating voltage 24 V F2 Y3 Y2 Y1 Fig 4 6 Set up and maintenance 6 1 Functional testing The safety function of the safety monitoring module must be tested The following conditions must be previously checked and met 1 Correct fixing 2 Check the integrity of the cable entry and connections 3 Check the safety monitoring module s enclosure for...

Page 5: ... 60947 5 5 Fig 8 Wire breakage and earth leakage in the control circuits are detected Category 2 PL d to DIN EN 13849 1 possible Dual channel emergency stop circuit with command devices to DIN EN ISO 13850 EN 418 and EN 60947 5 5 Fig 9 The control system recognises wire breakage and earth faults in the control circuit Cross wire shorts between the control circuits are not detected Category 4 PL e ...

Page 6: ...et switching capacity min 240 mW switching voltage min 24 VDC switching current min 10 mA For example the following safety sensors from Schmersal meet the requirements BNS 33 02z 2187 BNS 33 02zG 2187 BNS 260 02z BNS 260 02zG BNS 260 02 01z BNS 260 02 01zG When sensors with LED are wired in the control circuit protective circuit the following rated operating voltage must be observed and respected ...

Page 7: ... construction conform to the applicable European Directives Name of the component SRB 304ST Description of the component Safety monitoring module for emergency stop circuits guard door monitoring magnetic safety switches and AOPDs Relevant Directives Machinery Directive EMC Directive RoHS Directive 2006 42 EC 2014 30 EU 2011 65 EU Applied standards EN 60947 5 1 2004 AC 2005 A1 2009 EN 60947 5 3 20...

Page 8: ... A Schmersal GmbH Co KG Möddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal com ...