8.3  Sensor configuration

Dual-channel control of a safety-related electronic (micro-

processor-based) safety guard with p-type transistor outputs  

e.g. AOPD's to EN IEC 61496 (see Fig. 10)

• 

Wire breakage and earth leakage in the control circuits are detected.

• 

Cross-wire shorts between the control circuits are usually detected 

by the safety guards. The safety-monitoring module therefore is not 

equipped with a cross-wire short detection here.

• 

Control category: 3 to EN 954-1

• 

If cross-wire shorts in the control circuits are detected by the  

safety guard:  

– control category 4 to EN 954-1:1997  

– control category 4 – PL e to DIN EN ISO 13 849-1 possible.

Single-channel emergency stop circuit with command devices  

to DIN EN ISO 13850 (EN 418) and EN 60947-5-5 (Fig. 11)

• 

Wire breakage and earth leakage in the control circuits are detected.

• 

Control category: 2 to EN 954-1

• 

Category 3 – PL d to DIN EN 13849-1 possible

Dual-channel emergency stop circuit with command devices  

to DIN EN ISO 13850 (EN 418) and EN 60947-5-5 (Fig. 12)

• 

Wire breakage and earth leakage in the control circuits are detected.

• 

Cross-wire shorts between the control circuits are not detected.

• 

Control category: 3 to EN 954-1

• 

Control category 4 – PL e to DIN EN 13849-1 possible  

(with protective wiring).

 

S12

+24V

B1

+24V

S22

S21

S12

S11

B1

S12

S22

S21

S12

S11

B1

S31

S22

S21

Fig. 10

Fig. 11

Fig. 12

Dual-channel emergency stop circuit with command devices  

to DIN EN ISO 13850 (EN 418) and EN 60947-5-5 (Fig. 13)

• 

Wire breakage and earth leakage in the control circuits are detected.

• 

Cross-wire shorts between the control circuits are detected.

• 

Control category: 4 to EN 954-1

• 

Category 4 – PL "e" to DIN EN ISO 13849-1 possible

Single-channel guard door monitoring circuit with interlocking 

devices to EN 1088 (Fig. 14)

• 

At least one contact with positive break required

• 

Wire breakage and earth leakage in the control circuits are detected.

• 

Control category: 2 to EN 954-1

• 

Category 2 – PL d to DIN EN ISO 13849-1 possible

Dual-channel guard door monitoring circuit with interlocking 

device to EN 1088 (Fig. 15)

• 

With at least one positive-break position switch

• 

Wire breakage and earth leakage in the control circuits are detected.

• 

Cross-wire shorts between the control circuits are not detected.

• 

Control category: 3 to EN 954-1

• 

Control category 4 – PL e to DIN EN 13849-1 possible  

(with protective wiring).

 

S12

S11

S22

S21

B1

S31

S12

S11

B1

S12

S22

S21

S12

S11

B1

S31

S22

S21

Fig. 13

Fig. 14

Fig. 15

Dual-channel guard door monitoring circuit with interlocking 

device to EN 1088 (Fig. 16)

• 

With at least one positive-break position switch

• 

Wire breakage and earth leakage in the control circuits are detected.

• 

Cross-wire shorts between the control circuits are detected.

• 

Control category: 4 to EN 954-1

• 

Category 4 – PL e to DIN EN ISO 13849-1 possible

Dual-channel control of magnetic safety switches to EN 60 947-5-3 

(see Fig. 17)

• 

Wire breakage and earth leakage in the control circuits are detected.

• 

Cross-wire shorts between the control circuits are not detected.

• 

Control category: 3 to EN 954-1

• 

Category 3 – PL "e" to DIN EN ISO 13849-1 possible

Dual-channel control of magnetic safety switches to EN 60 947-5-3 

(see Fig. 18)

• 

Wire breakage and earth leakage in the control circuits are detected.

• 

Cross-wire shorts between the control circuits are detected.

• 

Control category: 3 to EN 954-1

• 

Category 3 – PL "e" to DIN EN ISO 13849-1 possible

 

S12

S11

S22

S21

B1

S31

B1

S31

S12

S11

S22

S21

S22

S21

S12

S11

B1

S31

Fig. 16

Fig. 17

Fig. 18

Summary of Contents for SRB 324ST/R V.3

Page 1: ...h the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General...

Page 2: ...nder observation of a B10d value assessment also refer to Requirements to DIN EN ISO 13849 1 control category 3 PL d to DIN EN ISO 13849 1 corresponds to SIL 2 to DIN EN 61508 2 corresponds to SILCL 2...

Page 3: ...operating days per year hop average number of operating hours per day tcycle average demand rate of the safety function in s e g 4 per hour 1 per 15 min 900 s Specifications can vary depending on the...

Page 4: ...Fig 3 New adjustable drop out delays and cross wire short monitoring for version V 3 See Fig 4 Tolerance 2 DIP switch setting Drop out delay DIP switch setting Drop out delay ON 1 2 3 4 0 1 s ON 1 2 3...

Page 5: ...ons 8 Appendix 8 1 Wiring examples Dual channel control shownfora guard door monitor with two contacts A and B where at least one is a positive break contact with external reset button J see Fig 7 Rel...

Page 6: ...ontrol category 4 to EN 954 1 Category 4 PL e to DIN EN ISO 13849 1 possible Single channel guard door monitoring circuit with interlocking devices to EN 1088 Fig 14 At least one contact with positive...

Page 7: ...4 Actuator configuration Single channel control with feedback circuit Fig 19 Suitable for increase in capacity or number of contacts by means of contactors or relays with positive guided contacts S F...

Page 8: ...elan de We hereby certify that the hereafter described safety components both in its basic design and construction conforms to the applicable European Directives Place and date of issue Wuppertal Oct...

Reviews: