22
Operating instructions
Safety-monitoring module
SRB-E-232ST
EN
7.5 Sensor configuration
Single channel signal processing
+24
VDC
S12 S22
S12 S22
S11 S21
Rotary knob
position
Function
4
Reset button (detection of the trailing edge)
10
Reset without monitoring / autostart
Dual channel signal processing NC / NC
With cross-wire monitoring
(Category 4 – PL e to ISO 13849-1 possible)
S12 S22
S11 S21
S12 S22
S11 S21
Rotary knob
position
Cross-wire
monitoring
Synchronisation
1
Yes
Yes
2
Yes
No
7
Yes
Yes
8
Yes
No
Without cross-wire monitoring
(Cat. 4 - PL e to ISO 13849-1 only possible with protective wiring)
S12 S22
S11 S21
S12 S22
S11 S21
+24
VDC
S12 S22
S12
+24V
S22
+24V
Rotary knob
position
Cross-wire
monitoring
Synchronisation
3
No
Yes
4
No
No
9
No
Yes
10
No
No
Dual channel signal processing NC / NO
(Category 4 – PL e to ISO 13849-1 possible)
S12 S22
S11 S21
+24
VDC
S12 S22
S12 S22
S11 S21
Rotary knob
position
Function
5
Reset button (detection of the trailing edge)
6
Reset without monitoring / autostart
8. Set-up and maintenance
8.1 Commissioning
The safety relay module features protection class IP54 for installation in
a switch cabinet.
The safety relay module is delivered ready for operation.
Application 1 is preset in the factory.
8.2 Functional testing
The safety function of the safety-monitoring module must be tested.
The following conditions must be previously checked and met:
1. Correct fixing
2. Check the integrity of the cable entry and connections
3. Check the safety-monitoring module's enclosure for damage
4. Check the electrical function of the connected sensor technology
and their influence on the safety-monitoring module and the
downstream actuators
The safety relay module features self-test functions.
If a fault is detected, the system adopts a safe mode and leads,
if necessary, to undelayed deactivation of all safety outputs.
8.3 Behaviour in the case of faults
In the event of a fault the following procedure is recommended:
1. Identify faults according to flash codes from chapter 6.2.
2. Rectify the fault if it is described in the table.
3. Switch operating voltage off and on and erase fault mode.
If fault could not be rectified, please contact the manufacturer.