SRB NA-R-C.39/ST2

Operating instructions

Safety-monitoring module

EN

2.5 

Safety classification

Standards:

EN ISO 13849-1, IEC 61508, 

 

EN 60947-5-1

PL:

Stop 0: up to e

Control category:

Stop 0: up to 4

DC:

Stop 0: 99% (high)

CCF:

> 65 points

SIL:

Stop 0: up to 3

Service life:

20 years

B

10d

 value (for one channel):

Low voltages range 20%: 20,000,000

40%: 7,500,000

60%: 2,500,000

80%: 1,000,000

Maximum load 100%: 400,000

MTTF

B

d x

x

h

s/h

3600

d

10d

op

op

op

n

0,1 x n

op

t

cycle

For an average annual demand rate of n

op

 = 126,720 cycles per year, 

Performance Level PL e can be obtained at maximum load.

n

op

  =  average number of activations per year

d

op

  = average number of operating days per year

h

op

  =  average number of operating hours per day

t

cycle

  =   average demand rate of the safety function in s 

(e.g. 4 × per hour = 1 × per 15 min. = 900 s)

(Specifications can vary depending on the application-specific 

 

parameters h

op

, d

op

 and t

cycle

 as well as the load.)

3  Mounting

3.1  General mounting instructions

Mounting: snaps onto standard DIN rails to EN 60715.

Snap the bottom of the enclosure slightly tilted forwards in the  

DIN rail and push up until it latches in position.

3.2  Dimensions

All measurements in mm.

Device dimensions (H/W/D): 83 x 45 x 140 mm

4  Electrical connection

4.1  General information for electrical connection

Wiring examples: see appendix

The electrical connection may only be carried out by  

authorised personnel in a de-energised condition.

5  Operating principle and settings

5.1  LED functions

• K1: Status start relay

• K2: Status channel 1

• K3: Status channel 2

• Ui: Status internal operating voltage (LED is on, when the 

 

operating voltage on the terminals A1-A2 is ON and the fuse 

 

has not been triggered)

• U

B

: Status operating voltage (LED is on, when the operating 

voltage on the terminals A1-A2 is ON)

5.2  Description of the terminals

Voltages:

A1

A2

L13

D2

+24 VDC / 24 VAC

0 VDC / 24 VAC

+24 VDC

0 VDC

Inputs:

T11-T12

T11-T22

Input channel 1 (+)

Input channel 2 (+)

Outputs:

13-14

23-24

33-34

L14

First safety enabling circuit

Second safety enabling circuit

Third safety enabling circuit

Signalling output K2 / K3

Start:

T33-T34

X1-X2

Wire bridge

Feedback circuit

T33

T11

SRB-NA-R-C.39/ST2-24V

34

T12

24

T22

L13

D2

K3

K2

UB

K1

Ui

T34

33

X1

23

X2

14

13

A2

A1

L14

Fig. 1

5.3  Notes

Semi-conductor output (Fig. 2)

• 

The semi-conductor output L14 is galvanically separated from the 

other parts of the SRB safety monitoring module.The voltage is 

 

supplied through the terminals L13 and D2.

• The semi-conductor output L14 switch when relay K2 and K3 

 

(of the channels 1 and 2) are activated.

L13

24 VDC

D2

0 V

Fig. 2

6  Set-up and maintenance

6.1  Functional testing

The safety function of the safety-monitoring module must be tested. 

The following conditions must be previously checked and met:

1. Correct fixing

2. Check the integrity of the cable entry and connections

3. Check the safety-monitoring module's enclosure for damage.

4.  Check the electrical function of the connected sensors and  

their influence on the safety-monitoring module and the 

 

downstream actuators

6.2  Maintenance

A regular visual inspection and functional test, including the following 

steps, is recommended:

1. Check the correct fixing of the safety-monitoring module

2. Check the cable for damages

3. Check electrical function

Damaged or defective components must be replaced.