Xact Small Tank Monitoring System
7
Setting Alarm Levels in Event Monitoring Mode
Only active in Event Monitoring Mode.
Alarm levels can only be adjusted at the tank. It is imperative that you
set these correctly, since revisiting the tank is required to make changes.
Refill Alarm
. Refill is the first alarm level you will set. This percentage
will be your first notification on the website of tank draw-down.
Critical
Alarm
. Critical is the second notification of tank draw-down.
This alarm report will also be made a second time, 24 hours later, if no
Refill event occurs. Set the threshold of this alarm to ensure that you will
have plenty of time to get to this tank before it is empty.
Select the correct percentages by sliding the bar, and Tap the
Accept
button to continue.
Setting Measurement Cycles in Scheduled Monitoring Mode
Only active in Scheduled Monitoring Mode.
On the following screens you will setup a schedule that determines how
often the Xact Tank Monitoring System will take measurements and report
the results.
Be advised that a schedule with higher numbers of measurements will
produce higher monthly monitoring costs for the system.
First indicate the day(s) of the week the system should measure and
report. Tap the
Accept
button to continue.
Next select the hour(s) of the day in which you want measurements to
be taken. The Xact Tank Monitoring System will wake up at a random time
during the selected hour(s) to measure and report the fill level of the tank.
For the most accurate measurement results you should select hours
that the tank will not be active with filling or dispensing. For example
before and after business hours or during any other period of time that is
known to be a quiet or inactive period for the tank. Tap the
Accept
button
to continue.