background image

 

 

page 

11

 

 

I

NSTALLATION

 

The company accepts no responsibility for damage caused by wrong connections or by 
operations not described in this manual. 

The BATTERY BOX electrical specifications are shown on the data plate at the back of the 
device. 

 

 

I

NSTALLATION PROCEDURE

 

Before connecting the BATTERY BOX to the UPS ensure that the following notes are 
complied with: 

 

Install the BATTERY BOX on a flat and stable surface. 

 

Avoid placing it where it will be exposed to direct sunlight or hot air 

 

Keep ambient temperature between 0°C and 40°C    

N.B.:

  the  BATTERY  BOX  can  operate  with  ambient  temperature  between  0°C  and 

40°C. The optimal operating temperature of the batteries contained in the BATTERY 
BOX is between 20 and 25°C. While the operating life of the batteries is on average 4 
years with ambient temperature of 20°C, battery life is halved with the temperature at 
30°C. 

 

The ambient relative humidity must not exceed 90%. 

 

Avoid dusty environments. 

 

Take care to position the BATTERY BOX with the front and the back at least 10 cm 
from  walls  and  ensure  that  objects  are  not  placed  on  the  air  slots,  so  as  to  allow 
adequate ventilation. 

 

The cable connecting the BATTERY BOX to the UPS cannot be extended by the user. 
The supplier should be contacted if this is required.  

 

 

C

ONNECTING THE 

BATTERY

 

BOX 

 

Check that the BATTERY BOX battery voltage is the same as the voltage allowed by 

the  UPS  (check  the  data  plate  at  the  back  of  the  BATTERY  BOX  and  the  UPS 
manual) 

 

Depending  on  requirements,  connect  the  BATTERY  BOX  to  the  UPS  or  to  another 

BATTERY BOX by means of the expansion cable provided 

 

Insert the two fuses provided into the fuse-holder disconnecting switches at the back 

of the BATTERY BOX. Close the disconnecting switches. 

 

(only  for  the  version  with  battery  charger)

:  connect  the  power  cable  to  the 

BATTERY  BOX  and  o  the  mains.  The  LED  indicating  mains  present  will  light  up 
immediately.  The  LED  indicating  battery  charger  operating  will  also  light  up  after  a 
few seconds’ delay.

 

Summary of Contents for GENIO Dual Maxi Series

Page 1: ...USER MANUAL UNINTERRUPTIBLE POWER SUPPLY Series GENIO Dual Maxi Battery boxes USBB240A3 USBB240A5 USBC240A5...

Page 2: ...tructions for the use and installation of the BATTERY BOX for UPSs To get the most out of this device please read these instructions and follow them carefully Keep this manual near the BATTERY BOX No...

Page 3: ...ESCRIPTION OF OPERATION 6 INSTALLATION 7 OPENING THE PACKAGING AND CHECKING ITS CONTENTS 7 TOWER VERSION 8 RACK VERSION 9 INSTALLATION PROCEDURE 11 CONNECTING THE BATTERY BOX 11 MULTIPLE EXPANSIONS 12...

Page 4: ...to requirements by using the handles kit The two different versions of the product are shown below JSDL240PA3 JSDL240PA5 JSDL240CA5 Nominal capacity Ah 7 9 9 Dimensions H x L x P mm 455 x 175 x 660 1...

Page 5: ...TERY BOX Release slots Extractable rotatable mask Removable front panel Front view Ventilation grid IEC 10A input only in versions with battery charger Fuse holder disconnecting switches Connectors fo...

Page 6: ...n the type of UPS the BATTERY BOX is intended for The utmost care must therefore be taken to ensure that the battery voltage of the BATTERY BOX is the same as the voltage allowed by the UPS The BATTER...

Page 7: ...check the contents The packaging should contain the following BATTERY BOX Power cable only for models with battery charger Battery expansion cable Handles kit for rack version 3 plastic covers upper...

Page 8: ...NOT CONNECTED TO THE ELECTRICITY MAINS TO THE UPS OR TO ANY OTHER BATTERY BOXES Once removed from the packaging the BATTERY BOX is ready for installation in tower configuration All that is needed to c...

Page 9: ...erations for the remaining feet The exact sequence to follow is shown at the side 2 Once all the feet have been removed the mask must then be rotated Insert the keys provided in the release slots loca...

Page 10: ...with the screws as shown in the figure at the side NOTE The BATTERY BOX is compatible for mounting in standard rack cabinets of 600mm x 800mm or more in width Support brackets guides with L shaped sup...

Page 11: ...ive humidity must not exceed 90 Avoid dusty environments Take care to position the BATTERY BOX with the front and the back at least 10 cm from walls and ensure that objects are not placed on the air s...

Page 12: ...PACITY SETTINGS SOFTWARE CONFIGURATION When one or several BATTERY BOXES have been installed the UPS must be configured to update the nominal capacity value total Ah of batteries within the UPS extern...

Page 13: ...y No mains voltage black out Check that voltage is present in the plug used to connect the BATTERY BOX by trying it with a table lamp for example Battery charger input fuse has blown Call SERVICE to r...

Page 14: ...oltage Dimensions H x L x W mm 455 x 175 x 660 5 Weight Kg 67 BASIC MODELS JSDL240PA3 JSDL240PA5 BATTERY Nominal voltage Vdc 240 Nominal Ah Ah 7 9 End of charge voltage Vdc 273 No of batteries V Ah 20...

Page 15: ...page 15...

Page 16: ...MAN_USBB240A3 USBC240xx_EN_2011_03 doc 0MNSDL240NP5LUA...