33
A
UTO POWER OFF
If, during battery operation, the percentage of the load powered by the system falls below the selected threshold, after 40 seconds the
system automatically switches off if the function is enabled; the system continues to function normally via battery if the function is
disabled [Default → Function DISABLED].
E
NABLE DEFAULT
IN
SIGNALS
The user can enable the default settings for programmable input signals. Refer to
Table 4.2
, “Setting for input signals (default
configured from the display panel)” paragraph.
I
NVERTER OUTPUT SETTINGS
From this page, the user can set the output voltage of the inverter and the output frequency.
WARNING:
These settings must be correctly configured by expert personnel only; improper settings can lead to severe damage of
the load connected to the UPS output.
General configuration page 2: Output voltage and frequency setting
NOTE:
by selecting a low output voltage (200, 208 and 220V), the output power will be consequently reduced.
Refer to the graph below: