Start-up
03.00 | EGI | Assembly and Operating Manual | en | 1396645
43
6.2 Commissioning the product
System integration
The communication protocol "SCHUNK Flexible Protocol" is
available for operation within the plant.
For further information, see Software manual "EGI with PROFINET,
EtherCAT or EtherNet/IP interface".
Ø
Configuring the hardware:
Assigning the IP address.
Enter a unique device name.
Ø
Switch on the logic voltage.
✓
LED LOG lights up green.
Ø
Switch on the power voltage.
✓
LED PWR lights up green.
Ø
Make sure that the product is ready-to-operate and not
reporting any errors.
✓
LED MS lights up green (product status).
✓
LED NS lights up green (network status).
Ø
If necessary, rectify the error reported,
Ø
Start the control software.
Ø
Import device description file into the control system.
Ø
Add the product to the hardware configuration.
Ø
Load the hardware configuration into the control system.
Ø
Assign the hardware name to the product.
NOTE
For a detailed description of incorporating the product into a
control, see the documentation of the relevant control
manufacturer.