32
DANGER!
The conversion for the operation of the boiler
with a type of gas other than that specifically
required in the order, must be performed by
professionally qualified personnel, in com
-
pliance with the standards and regulations
in force.
The manufacturer cannot be held liable for
any damage resulting from a conversion
operation that is incorrect or not performed
in compliance with the laws in force and/or
with the instructions given.
ATTENTION!
After performing the conversion for the op-
eration of the boiler with a type of gas (e.g.
propane gas) other than that specifically
requested when ordering, the appliance will
only work with this new type of gas.
ATTENTION!
Indications for propane gas-fired appliances
Make sure that the gas tank has been deaer-
ated before installing the appliance.
For state-of-the-art deaeration of the tank,
contact the LPG supplier or a person qualified
in compliance with law.
If the tank has not been professionally deaer-
ated, ignition problems could arise.
In that case, contact the supplier of the LPG
tank.
Gas Conversion
The boilers are produced for the type of gas specifically requested
upon ordering.
In order to change the gas one must change the Factory
parameter FH and FL.
(*) for values, see TABLE NOZZLES - PRESSURE-FLOW
-
when the conversion is complete, fill in the information
required on the label supplied in the documentation
envelope and apply it next to the technical data label of
the boiler.
For the conversion of the boiler from a gas to an other one it is
necessary to proceed as follows:
1. Remove the front casing
2. Set the maximum pressure adjusting screw (S.) at
approximately half range and screw of a turn the minimum
pressure adjusting screw (R), as shown on page 3.12.
3. Try to ignite the boiler: if it fails proceed unscrewing of a
turn the maximum pressure adjusting screw (S) and retry
the ignition. Repeat more times the operation, till the igni
tion of the boiler.
4. Adjust the CO2 value according to the type of gas as
described in the paragraph “3.12 - Adjustment of the
burner.
4.3 - ADAPTATION
TO THE UsE OF OTHER GAs
EXAMPLE OF COMPILATION
M
E
T
H
A
N
E
P
R
O
P
A
N
E
Simb. Desciption
Value
FH
Fan Speed:
maximum
(*)
FL
Ventilatore:
minimum
(*)