Maintenance instructions
( Num ) =
see legenda Par. 2.2
CODE
DIsPLAY
E8
CODE
PRIORITY DEsCRIPTION
sOLUTION
E13
DHW sensor failure (only if the boiler is
combined with an external storage tank)
Check the sensor’s efficiency and/or its
wiring
E32
Mains voltage < 190 Vac
Check that the mains voltage is <190 Vac,
if the mains voltage is correct replace
the control board.
E15
Difference between the heating tempera-
ture sensor (SR) and the heating return
sensor (SRR) > 35°C.
Check the installation
E14
HEATING RETURN SENSOR (22)
Failure of the heating return sensor
(SRR)
Check the efficiency of the sensor and/
or wiring
(22)
E40
INSUFFICIENT WATER CIRCULATION
(∆t > 35° C)
Check the operation the pump
(12)
and
its speed - remove any obstructions in the
heating system - clean heat exchanger
health encrusted.
E06
HIGH TEMPERATURE
Over high temperature detected by
the heating sensor (SR) (>95°C)
Check the operation the pump and possi-
bly clean the heat exchanger. (24)
E05
Loss of flame signal during boiler
operation
Press the reset key on the panel
E04
No flame detected during the ignition
phase.
Press the reset key on the
control panel
E24
FAN SPEED OUT OF CONTROL
Alteration of the fan speed.
Fan speed is not achieved.
Check the operation of the fan (18) and
connections
E26
SPEED OUT OF CONTROL
Alteration of the fan speed
Fan speed hightest than that required
Check the operation of the fan (18) and
connections
E08
LACK OF WATER
Fill-up the water circuit
4.6 - ERROR CODEs
DIsplay Controller E8 (Optional)
For error codes relating to the heating system, refer to the
section “Faults Finding” in Instructions for use supplied with
the contoller E8.
Control panel
When indicator fault light,
press the BUTTON to view the error code on the display.