The following message should appear on the terminal:
The ALARM relay should pull in, holding its
"
b
"
contacts open. If the relay pulls in but no
message is received, check the terminal configuration. If neither occurs, turn off the power
and refer to the TROUBLESHOOTING guide.
The equal sign is a prompt indicating that communications with the relay are at Access
Level 0, the lowest of three access levels to the relay. The only command allowed at this
level is ACCESS, which admits you to Access Level 1, as described below.
Type the command
ACCESS
and press
<ENTER>.
At the prompt, enter the password
OTTER
and press
<ENTER>.
The prompt = > should appear, indicating that you have
established communications at Access Level 1.
The relay is shipped with demonstration settings which you may inspect using the SHOWSET
command. Type
SHOWSET
and press
<ENTER>
to view these settings. The terminal
should display the following:
A complete description of the settings appears under the SET command.
6-2
Maintenance and Testing
SEL-267D/167D Instruction Manual
Date Code 920326
Summary of Contents for SEL-167D
Page 3: ......
Page 6: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 51: ...LOGIC DIAGRAMS Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 31 ...
Page 52: ...Date Code 920326 Specifications 2 32 SEL 267D 167D Instruction Manual ...
Page 53: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 33 ...
Page 54: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 34 ...
Page 88: ...SAMPLE EVENT REPORT ...
Page 114: ......
Page 115: ......