EXPLANATION OF EVENT REPORT
Currents and voltages are in primary Amps and kV. Rows are ¼ cycle apart. Time runs down
page. Obtain phasor RMS value and angle using any entry as the Y-component, and the entry
immediatey underneath as the X-component. For example, from bottom rows, IAY = -275,
IAX = -1206. Therefore, IA = 1237 amps RMS primary, at an angle of ATAN(-275/-1206) =
-167°, with respect to the sampling clock.
<FID>
Row 2 shows the Firmware Identification Data. This line varies according to
version.
<Relays>
Columns show states of internal relay elements
---> Designators
50P : phase overcurrent . . . . . . . . : 50P1, 50P2, 50P3
---> 1,2,3
67P
: directional phase overcurrent
: 67P1, 67P2, 67P3
---> 1,2,3
51P
: phase time-overcurrent . . . . . . . : 51PT
---> T
50N : inst ground overcurrent . . . . . . : 50N1, 50N2, 50N3
---> 1,2,3
67N : directional ground overcurrent : 67N1, 67N2, 67N3
---> 1,2,3
51N : ground time-overcurrent . . . . . . : 51NT
---> T
<Outputs> Columns show states of output contacts: ON = "*" , OFF =
"
.
"
TP-TRIP, CL=CLOSE, A1-A4=PROGRAMMABLE, AL=ALARM
<Inputs>
Columns show states of input contacts:
DT=DIRECT TRIP, PT=PERMISSIVE TRIP, BT=BLOCK TRIP, DC=DIRECT CLOSE,
52A=PCB A-CONTACT, ET=EXTERNAL TRIGGER (event report)
<Event>
Event type is one of the following:
AG, BG, CG = single-phase, AB, BC, CA = 2-phase
ABG, BCG, CAG = 2-phase to ground, ABC = 3-phase followed by a T if a
TRIP triggered the report
Other indications are TRIP = triggered by TRIP output and EXT = exter-
<Location>
nally or otherwise triggered
Distance to fault in miles. Indeterminate distance is 999999.
<Ohms Sec>
Distance to fault in secondary ohms. Indeterminate ohms is 999999.
<Duration>
Fault duration determined from relay element(s) pickup time
<Flt Current> Max phase current (primary amps) taken near middle of fault
<Targets>
The targets indicate the relay elements that caused the trip. These targets
are the same as the targets displayed on the front panel of the SEL-167D
via the TARGET 0 command. The targets field indicates any combination of
the following:
P1:
Zone 1 phase fault
P3: Zone 3 phase fault
G1:
Zone 3 ground fault
P2:
Zone 1 ground fault
Zone 2 phase fault
G3:
51P: Phase time-overcurrent trip
G2:
Zone 2 ground fault
51N: Residual time-overcurrent trip
R1,X1,R0,X0
Primary series impedance settings for transmission line
LL
Line length corresponding to specified line impedances
ROS,XOS
Zero-sequence source impedance (used by fault locator only)
CTR, PTR
Current and potential transformer ratios (XTR:1)
M T A
Maximum torque angle for the directional elements
LOCAT
Enable or disable fault locator (Y/N)
DATC
Demand ammeter time constant
DCTH
Demand current threshold
790I1,2,3,RS
Three-shot recloser Open and Reset intervals
51PP,TD,C,TC
Phase time-overcurrent pickup, Time Dial, Curve, Torque Control
50P1,2,3
Phase inst-overcurrent pickup settings Zones 1, 2 and 3
Z1DP,2,3
Zones 1, 2 and 3 timer settings for three- and two-phase faults
51NP,TD,C,TC
GND time-overcurrent Pickup, Time Dial, Curve, Torque Control
50N1,2,3
Z1DG,2,3
TDUR
52BT
ZONE3
67NE, PE
32QE, IE
TIME1,2
AUTO
RINGS
See LOGIC command for a description of mask setting.
Ground inst-overcurrent pickup settings Zones 1, 2 and 3
Zone timers for ground faults
Minimum trip duration timer
528 delay setting (for switch-onto-fault coordination)
Directional orientation of ALL Zone 3 elements (Fwd/Rvs)
Ground fault directionality from (V2, I2), or (IP, IO)
Ground and phase fault torque control enables
Communications port timeout intervals (automatic log-off)
Port assignment for automatic message transmissions
Number of rings to wait before modem answers telephone
<Logic Settings>
Summary of Contents for SEL-167D
Page 3: ......
Page 6: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 51: ...LOGIC DIAGRAMS Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 31 ...
Page 52: ...Date Code 920326 Specifications 2 32 SEL 267D 167D Instruction Manual ...
Page 53: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 33 ...
Page 54: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 34 ...
Page 88: ...SAMPLE EVENT REPORT ...
Page 114: ......
Page 115: ......