INTRODUCTION
GETTING STARTED
This instruction manual applies to SEL-167D and SEL-267D relays. The SEL-267D and
SEL-167D relays have identical protection features, but use different hardware designs.
Where there are differences between the two relay models, both relays are described.
If you are not familiar with the relay, we suggest that you read this introduction, then perform
the Initial Checkout Procedure in Section 6: MAINTENANCE & TESTING.
OVERVIEW
The SEL-267D PHASE AND GROUND DIRECTIONAL OVERCURRENT RELAY WITH
FAULT LOCATOR may be applied to protect transmission, subtransmission and distribution
lines. The SEL-267D relay is intended for use on grounded systems with open-delta
connected potential transformers. Use the SEL-267 relay where wye-connected potential
transformers are applied.
The features of the SEL-267D relay include:
Directional Overcurrent Protection for Phase and Ground Faults
Versatile User-Programmable Logic
Three-Shot Reclosing with Fuse Saving Capability
Fault Locating
Event Recording
Automatic Self Testing
Metering, Including Demand
Target Indicators for Faults and Testing
Time Code Input
Front and Rear Panel Communication Ports for Local and Remote Access
Compact and Economical
Date Code 920326
Introduction
SEL-267D/167D Instruction Manual
1-1
Summary of Contents for SEL-167D
Page 3: ......
Page 6: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 51: ...LOGIC DIAGRAMS Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 31 ...
Page 52: ...Date Code 920326 Specifications 2 32 SEL 267D 167D Instruction Manual ...
Page 53: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 33 ...
Page 54: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 34 ...
Page 88: ...SAMPLE EVENT REPORT ...
Page 114: ......
Page 115: ......